1) Preparation of pipings
1. Cut the pipes and the cable.
• Use the accessory piping kit or the pipes pur-
chased locally.
• Measure the distance between the indoor and
the outdoor unit.
• Cut the pipes a little longer than the measured
distance.
• Cut the cable 1.5m longer than the length of the
pipe.
2. Remove burrs.
• Remove burrs from cut edges of pipes.
• Turn the pipe end toward down to avoid the
metal powder entering the pipe.
Caution:
If burrs are not removed, they may cause a gas
leakage.
3. Flaring the pipes.
• Insert the flare nuts, mounted on the connection
ports of both indoor and outdoor unit, onto the
copper pipes. Some refrgerant gas may leak,
when the flare nuts are removed from the indoor
unit, as some gas is charged to prevent the
inside of the pipe from rusting.
• Fit the copper pipe end into the Bar of flare tool
about 0~0.5mm higher. (See illustration)
• Flare the pipe ends.
4. Tape the flaring portion to protect it from the
dust or damages.
90
Slanted
Pipe cutter
Rough
Reamer
Pipe
Point down
"A"
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Bar
Yoke
Handle
Inclined
Cracked
Uneven
thickness
Surface
damaged
= Improper flaring =
When properly flared, the internal surface flare will
evenly shine and be of even thickness.
Since the flare part comes into contact with the connec-
tors, carefully check the flare finish.
"A"; ø12.7 mm (1/2")
→
0~0.5 mm
ø9.52 mm (3/8")
→
0~0.5 mm
ø6.35 mm (1/4")
→
0~0.5 mm
(2) Piping and Drainage of Indoor Unit
Содержание L2-C242GL0
Страница 13: ...Service Manual 13 Dimensions 900 1 225 370 L3 C482LL0 ...
Страница 18: ...18 Multi Air Conditioner Electronic Control Device Outdoor Unit MAIN P C B ASM L3 C362LL0 L3 C482LL0 ...
Страница 19: ...Service Manual 19 Electronic Control Device Display P C B ASM ...
Страница 20: ...20 Multi Air Conditioner Schematic Diagram Schematic Diagram Indoor Unit L3 C362LL0 L3 C482LL0 ...
Страница 21: ...Service Manual 21 Schematic Diagram L2 C362LL0 ...
Страница 22: ...22 Multi Air Conditioner Schematic Diagram Outdoor Unit L3 C362LL0 ...
Страница 23: ...Service Manual 23 Schematic Diagram L3 C482LL0 ...
Страница 75: ...P No 3828A20156P January 2005 Printed in Korea ...