Service Manual 49
Installation
2) Connection of Pipings
1. Remove the installation plate
• Pull the two '
∆
' marked portion of bottom of the
chassis and pull the installation plate out of chas-
sis.
2. Route the drain hose and the indoor tubing.
For left rear piping
3. Route the tubing and the drain hose straight
backwards(see figure).
4. Insert the connecting cable into the indoor
unit through the piping hole.
• Do not connect the cable to the indoor unit.
• Make a small loop with the cable for easy con-
nection later.
5. Tape the tubing, drain hose and the connecting
cable. Be sure that drain hose locates at the
lowest side of the bundle.
Locating at the upper side can be a reason that
drain water overflows drain pan inside the unit.
Installation plate
Pull
Pull
Connecting
cable
Gas side piping
Liquid side piping
Drain hose
• To remove the holder, press
the bottom of the chassis
near the holder upwards
and the tab is clear of its
hole.
• Turn it clockwise approx.
90° and remove it.
Tubing holder
Press
Pull
Содержание L2-C242GL0
Страница 13: ...Service Manual 13 Dimensions 900 1 225 370 L3 C482LL0 ...
Страница 18: ...18 Multi Air Conditioner Electronic Control Device Outdoor Unit MAIN P C B ASM L3 C362LL0 L3 C482LL0 ...
Страница 19: ...Service Manual 19 Electronic Control Device Display P C B ASM ...
Страница 20: ...20 Multi Air Conditioner Schematic Diagram Schematic Diagram Indoor Unit L3 C362LL0 L3 C482LL0 ...
Страница 21: ...Service Manual 21 Schematic Diagram L2 C362LL0 ...
Страница 22: ...22 Multi Air Conditioner Schematic Diagram Outdoor Unit L3 C362LL0 ...
Страница 23: ...Service Manual 23 Schematic Diagram L3 C482LL0 ...
Страница 75: ...P No 3828A20156P January 2005 Printed in Korea ...