6 Convertible Air Conditioner
Installation of Indoor, Outdoor Unit
3) Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
•
Rated performance for refrigerant line length of:7.5m
•
Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
•
Improper refrigerant charge may result in abnormal cycle.
•
Oil trap should be installed every 10 meters.
CAUTION
Model
HV-C186BLA0 5/8”(15.88mm) 1/4”(6.35mm)
7.5
30
5
20
25
HV-H186BLA0 5/8”(15.88mm) 1/4”(6.35mm)
7.5
30
5
20
30
HV-C246BLA0 5/8”(15.88mm) 1/4”(6.35mm)
7.5
30
5
20
35
HV-H246BLA0 5/8"(15.88mm) 1/4"(6.35mm)
7.5
30
5
20
40
*Additional
refrigerant(g/
m)
Pipe Size
(Diameter:Ø)
Length A(m)
Elevation B(m)
Standard
Max.
Standard
Max.
Gas
Liquid