12
Ceiling Concealed Duct Air Conditioner
Installation of Indoor, Outdoor Unit
INSTALLATION OF REMOTE CONTROL BOX
Install the remote control box and
cord correctly.
• Although the room temperature sensor is in the indoor unit, the remote control box should
be installed in such places away from direct sunlight and high humidity.
INSTALLATION OF THE REMOTE CONTROL BOX
• Select places that is not splashed by
water.
• Select control position after receiving
customer approval.
• The room temperature sensor of the
thermostat for temperature control is built
in the indoor unit.
• This remote controller equipped with liquid
crystal display. If this position is higher or
lower, display is difficult to see.
(The standard height is 1.5m high)
ROUTING OF THE REMOTE CONTROL CORD
• Keep the remote control cord away from
the refrigerant piping and the drain piping.
• To protect the remote control cord from
electrical noise, place the cord at least
5cm away from other power cables. (Audio
equipment, Television set, etc)
• If the remote control cord is secured to a
wall, provide a trap at the top of the cord to
prevent water droplets from running.
POINT OF REMOTE CONTROLLER INSTALLATION
ELECTRICAL WIRING TO THE INDOOR UNIT
Make sure that wire and terminal
numbers are matched on unit side
and remote controller side.
(Main board)
CN REMO
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m, use a wire size greater than 0.5mm
2
.
Remote controller
CN REMO
The position of the fixing screws
Wall
Installation paper
Fixing the
remote controller
Fixing the
connecting cable
Put the installation paper on the place and
determine the position and height of the fixing
screws of the deluxe wired remote controller.
• Refer to the printed side of the installation
paper.
Remove the installation paper before
installing the remote controller so that
it can fit into the right place.
* When installing the deluxe wired remote controller, do not install it so that it is buried to the wall.
(This can cause error in the temperature sensor)
* When installing multiple deluxe wired remote controllers horizontally in one location, leave a
minimum distance apart (20mm). (This can cause error in the temperature sensor)
* Do not install the cable with a distance of 50 m or longer. (This can cause communication error.)
* When installing the cable, check whether the connector between the remote controller and the
product is installed properly. The connector will not be connected when installed in opposite sides.
Содержание B42AWYN762
Страница 35: ...P No MFL62541002 ...