- 22 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Installation
Indoor
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually
according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit and the terminal No.
are the same as those of the indoor unit.)
Connecting the Cables
CAUTION:
• The above circuit diagram is subject to change without notice.
• The earth wire should be longer than the common wires.
• When installing, refer to the circuit diagram behind the panel front of the indoor unit.
• Connect the wires firmly so that they may not be pulled out easily.
• Connect the wires according to color codes, referring to the wiring diagram.
CAUTION: If a power plug is not
used, provide a circuit breaker
between power source and the unit
as shown by.
CAUTION: The power cord connected to the "A" unit should be selected according to
the following specifications(Type "B" approved by HAR or SAA).
The power connecting cable connecting the indoor and outdoor unit should be selected
according to the following specifications (Type "B" approved by HAR or SAA).
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breake
or time delay fuse.
18k
24k
2.5
2.5
Unit(A)
Indoor
Indoor
Cable Type(B)
H05VV-F
H05VV-F
NORMAL CROSS
-SECTIONAL AREA
Grade
(mm
2
)
18k
24k
2.5
2.5
Cable Type(B)
H07RN-F
H07RN-F
NORMAL
CROSS
-SECTIONAL
AREA
Grade
(mm
2
)
Содержание AS-W1863 Series
Страница 81: ...P No 3828A20195V October 2009 ...