- 37 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Operation
• Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
• Compressor off temp. = setting temp. +4°C
on temp. = setting temp. +2°C
• If compressor operates at some operation frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature r4°C above the setting temperature.
• Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 30°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 7
Step 6
Step 5
Step 4
Step 3
Step 2
Step 1
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Heating mode operation
Model
AS-W1863_ Series
25
38
47
65
80
87
92
AS-W2463_ Series
35
44
53
61
69
73
77
Comp. Operating frequency
Step 1
Step 2
Step 3
Step 4
Step 5(Fc)
Step 6
Step 7
Содержание AS-W1863 Series
Страница 81: ...P No 3828A20195V October 2009 ...