Service Manual
57
Troubleshooting Guide
2. Evacuation
(All amount of refrigerant leaked)
• Procedure
(1) Connect the vacuum pump to the center hose
of charge set center hose
(2) Evacuation for approximately one hour.
– Confirm that the gauge needle has moved
toward -76 cmHg (vacuum of 4 mmHg or less).
(3) Close the valve (Lo side) on the charge set,
turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).
(4) Disconnect the charge hose from the vacuum
pump.
– Vacuum pump oil.
If the vacuum pump oil becomes dirty or
depleted, replenish as needed.
Lo
Open
Open
Vacuum pump
3-Way
valve
Outdoor unit
Liquid side
Indoor unit
Gas side
3-Way
valve
CLOSE
OPEN
CAUTION:
Use vacuum pump equipped with check value
applied to be prevented from flowing back-
ward.
Содержание AS-C306MSeries
Страница 43: ...Service Manual 43 Schematic Diagram Heat Pump Series Outdoor Unit Model AS H306 Series 5 5 4 4 3 3 2 2 1 1 ...
Страница 44: ...44 Room Air Conditioner Schematic Diagram Model AS H366 Series ...
Страница 45: ...Service Manual 45 Schematic Diagram 5 5 4 4 3 3 2 2 1 1 Model AS C306 Series ...
Страница 46: ...46 Room Air Conditioner Schematic Diagram Model AS C366 Series ...
Страница 49: ...Service Manual 49 Schematic Diagram Electronic Control Device INDOOR UNIT P W B ASSEMBLY ...
Страница 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM ...
Страница 73: ...Service Manual 73 Memo ...
Страница 74: ...74 Room Air Conditioner Memo ...
Страница 75: ...P No 3828A20347D Printed in Korea ...