General Installation Guidelines
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL INSTALLATION GUIDELINES
Piping Materials and Handling
Table 9: ACR Copper Tubing Dimensions and Physical Characteristics
1-4
Nominal Pipe
Outside
Diameter (in)
Actual Outside
Diameter (in)
Drawn Temper
Annealed Temper
Nominal Wall
Thickness (in)
Weight (lb/ft)
Cubic ft per
Linear ft
Nominal Wall
Thickness (in)
Weight (lb/ft)
Cubic ft per
Linear ft
1/4
0.250
--
--
--
0.030
0.081
.00020
3/8
0.375
0.030
0.126
.00054
0.032
0.134
.00053
1/2
0.500
0.035
0.198
.00101
0.032
0.182
.00103
5/8
0.625
0.040
0.285
.00162
0.035
0.251
.00168
3/4
0.750
0.042
0.362
.00242
0.042
0.362
.00242
7/8
0.875
0.045
0.455
.00336
0.045
0.455
.00336
1-1/8
1.125
0.050
0.655
.00573
0.050
0.655
.00573
1
All dimensions provided are in accordance with ASTM B280 – Standard.
2
Design pressure = 551 psig.
3
ACR Tubing is available as hard drawn or annealed (soft) and are suitable for use with R410A refrigerant.
4
The Copper Tube Handbook, 2010, Copper Development Association Inc., 260 Madison Avenue, New York, NY 10016.
• Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
• Prevent dust, water or other contaminants from entering the piping during installation. Contaminants can cause mechanical failure.
Selecting Field-Supplied Copper Tubing
Copper is the only approved refrigerant pipe material for use with Duct Free System Single Zone products, and LG recommends seamless
phosphorous deoxidized ACR type copper pipe, hard-drawn rigid type “K” or “L”, or annealed-tempered, copper pipe.
• Drawn temper (rigid) ACR copper tubing is available in sizes 3/8 through 2-1/8 inches (ASTM B 280, clean, dry, and capped).
• Annealed temper (soft) ACR copper tubing is available in sizes 1/4 through 2-1/8 inches (ASTM B 280, clean, dry, and capped).
Tube wall thickness should meet local code requirements and be approved for an operating pressure of 551 psi. If local code does not
specify wall thickness, LG suggests using tube thickness per table below. When bending tubing, try to keep the number of bends to a minimum, and
use the largest radii possible to reduce the equivalent length of installed pipe; also, bending radii greater than ten (10) pipe diameters can minimize
pressure drop. Be sure no traps or sags are present when rolling out soft copper tubing coils.
Table 7: ACR Copper Tubing Material
Type
Seamless Phosphorous Deoxidized
Class
UNS C12200 DHP
Straight Lengths
H58 Temper
Coils
O60 Temper
OD (in)
1/4
3/8
1/2
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
Material
Rigid Type “K” or “L” and Soft ACR Acceptable
Rigid Type “K” or “L” Only
Min. Bend
Radius (in)
.563
.9375
1.5
2.25
3.0
3.0
3.5
4.0
4.5
Min. Wall
Thickness (in)
.03
.03
.035
.040
.042
.045
.050
.050
.050
Table 8: Piping Tube Thicknesses