11
Product Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL DATA
Table 2: Art Cool Premier Electrical Data
Electrical
Unit Model Nos.
Nom.
Tons
Compressor
Qty
Compressor(A)
Cool/Heat
Fan Qty
ODU Fan(A)
IDU Fan(A)
MCA(A)
MOP(A)
Art Cool Premier
LA090HYV1
3/4
1
8.3/8.3
1
0.40
0.40
11.2
15
LA120HYV1
1
1
8.3/8.3
1
0.40
0.40
11.2
15
LA180HYV1
1-1/2
1
14.5/14.5
1
0.50
0.30
19.0
25
LA240HYV1
2
1
14.5/14.5
1
0.50
0.30
19.0
25
For component model nos.
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity
ODU Fan = Outdoor Unit Fan Motor
IDU Fan = Indoor Unit Fan Motor
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Table 3: Art Cool Premier Models