REFRIGERANT PIPING CONNECTIONS
Connection Limitations
Single zone systems consist of one outdoor unit and one indoor unit.
One of the most critical elements of a single zone system is the refrigerant piping. Table 13 lists pipe length limits that must be followed in the
design of a Single Zone Wall Mount refrigerant pipe system. Refer to Figure 29 for maximum length and elevation of piping.
Table 14: Art Cool Premier Refrigerant Piping System Limitations
Figure 28: Example System Layout with LA120HYV1
Refrigerant Piping System Limitations
Pipe Length
(ELF = Equivalent Length
of pipe in Feet)
Longest total equivalent piping length
LA090HYV1 / LA120HYV1 LA180HYV1 / LA240HYV1
65.6 feet
98.4 feet
Shortest total equivalent piping length
6.6 feet
9.8 feet
Distance between fittings and indoor or
outdoor units
≥ 20 inches
≥ 20 inches
No additional refrigerant
41 feet
24.6 feet
Elevation
(All Elevation Limitations
are Measured in Actual
Feet)
If outdoor unit is above indoor unit
32.8 feet
65.6 feet
If outdoor unit is below indoor unit
32.8 feet
65.6 feet
Additional Refrigerant Needed (oz/ft)
0.22
0.38
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
32.81
32.81
65.62
Max Length = A
Max Elevation = B
65.62
Unit = Feet