Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Capacity of Power Supply Wiring (current)
Required Minimum Distance
1,2
100V or more
10A
12 inches
50A
20 inches
100A
40 inches
Exceeding 100A
60 inches
1
The figures above are based on parallel lengths up to 328 feet long. For lengths in excess of 328 feet, the distances will have to be recalculated in
direct proportion to the additional line lengths involved.
2
If the power supply waveform continues to exhibit some distortion, the space between the power wiring and communication cable must be in-
creased.
Table 13: Power Wire and Communications Cable Minimum Required Separation Allowable Distances.
Separating Power Wiring and Communication Cables
•
Avoid running the power wiring and communication cable alongside each other; there is a strong likelihood of operation malfunction
due to electrostatic and electromagnetic interference.
Do not run both in the same conduit.
• If running the power wiring and communication cable alongside each other cannot be avoided, see the table below for minimum required
distances.
•
Do not secure the power wiring and communication cables together. It will result in equipment malfunction.
•
Do not run the power wiring and the communication cable in the same conduit. It will result in equipment malfunction.