2. Wall Mounted
LCS
(Light Commercial System) Indoor unit
Indoor Units
8
_ Dip Switch & Group Control Setting
Group Control Setting
- This function is only for group control.
- Please don’t set this function in case of non-group control.
- This function is the Master or Slave setting function of indoor unit
- Set only one indoor unit to Master, set the others to slave.
- After setting Group Control of the product, turn off the power then turn it back on after
1 minute.
- Master checking whether the buzzer sounds, such as indoor rings below.
▶
Master: “Beep” (Buzzer sound 1 time)
▶
Slave: “Beep, Beep, Beep, Beep, Beep ” (Buzzer sounds 5 times)
2.2 Group Control 1
Wired remote controller 1 + Standard Indoor Units
(1) Group Control 1
1. It is possible to 16 indoor units(Max) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
GND
Signal
12 V
Master
Slave
Slave
Master
Display Error Message
Only connect serial signal and GND lines
between slave indoor unit
LGAP Network System
Slave