2. Specifications
7
MULTI V
Indoor Unit
Wall Mounted Unit (Standard)
* Model Name (A:Basic, N:Ionizer)
Type
Wall Mounted Unit
Model
Unit
ARNU09GSJ*4
ARNU12GSJ*4
Cooling Capacity
kW
2.8
3.6
kcal/h
2,400
3,100
Btu/h
9,600
12,300
Heating Capacity
kW
3.2
4.0
kcal/h
2,800
3,400
Btu/h
10,900
13,600
Power Input (H / M / L)
W
13 / 12 / 9
15 / 13 / 11
Dimensions
(W×H×D)
Body
mm
837 × 308 × 189
837 × 308 × 189
inch
32-15/16 x 12-1/8 x 7-7/16
32-15/16 x 12-1/8 x 7-7/16
Shipping
mm
892 × 381 × 249
892 × 381 × 249
inch
35-1/8 × 15 × 9-13/16
35-1/8 × 15 × 9-13/16
Coil
Rows × Columns × FPI
2 × 15 × 19
2 × 15 × 19
Face Area
m²
0.19
0.19
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output × Number
W
30 × 1
30 × 1
Running Current
A
0.25
0.25
Air Flow Rate(H / M / L)
m³/min
7.8 / 7.2 / 5.9
8.5 / 7.8 / 6.8
ft³/min
275 / 254 / 208
300 / 254 / 240
Drive
Direct
Direct
Motor type
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Air Filter
Resin Net(washable)
Resin Net(washable)
Safety Device
Fuse
Fuse
Pipe Connections
Liquid Side
mm (inch)
Ø 6.35 (1/4)
Ø 6.35 (1/4)
Gas Side
mm (inch)
Ø 12.7 (1/2)
Ø 12.7 (1/2)
Drain Pipe(ID)
mm (inch)
16 (5/8)
16 (5/8)
Weight
Body
kg (lbs)
8.5 (18.7)
8.5 (18.7)
Shipping
kg (lbs)
11.3 (24.9)
11.3 (24.9)
Sound Pressure Levels (H / M / L)
dB(A)
34 / 32 / 28
37 / 34 / 30
Sound Power Levels (H / M / L)
dB(A)
55 / 54 / 52
55 / 54 / 53
Power Supply
Ø, V, Hz
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
Transmission cable
mm²
1.0 ~ 1.5 × 2C
1.0 ~ 1.5 × 2C
Color
White
White
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoot Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoot Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.