10. Installation

 

53

MULTI V

 

Indoor Unit

Wall Mounted Unit (Standard)   

Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average 

temperature.

Do not install the remote controller where it 

can be affected by :

– Drafts, or dead spots behind doors and in corners.
– Hot or cold air from ducts.
– Radiant heat from sun or appliances.
– Concealed pipes and chimneys.
– Uncontrolled areas such as an outside wall behind the 

remote controller.

– This remote controller is equipped with a seven segment 

LED. display. For proper display of the remote controller 

LED's, the remote controller should be installed properly.
(The standard height is 1.2~1.5 m from floor level.)

5feet

(1.5meters)

no

no

no

yes

Содержание ARNU15GSJA4

Страница 1: ...d MULTI V Indoor Unit 1 List of functions 2 Specifications 3 Dimensions 4 Piping Diagrams 5 Wiring Diagrams 6 Capacity Tables 7 Air Velocity and Temperature Distribution 8 Electric Characteristics 9 Sound Levels 10 Installation ...

Страница 2: ...dry operation O Convenience Auto changeover O Heat recovery Auto cleaning O Auto operation artificial intelligence O Heat pump or Cooling only Auto restart operation O Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O External On Off O Wi Fi O Note 1 O Applied X Not Applied Accessory model name Installed at field ordered and purchas...

Страница 3: ...dry operation O Convenience Auto changeover O Heat recovery Auto cleaning O Auto operation artificial intelligence O Heat pump or Cooling only Auto restart operation O Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O External On Off O Wi Fi O Note 1 O Applied X Not Applied Accessory model name Installed at field ordered and purchas...

Страница 4: ...nce Auto changeover O Heat recovery Auto cleaning O Auto operation artificial intelligence O Heat pump or Cooling only Auto restart operation Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O External On Off O Note 1 O Applied X Not Applied Accessory model name Installed at field ordered and purchased separately by the corresponding...

Страница 5: ...back O PDRYCB300 O PDRYCB500 Dry Contact For Modbus O Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units PSNFP14A0 Connected with the Indoor Units ETC Remote temperature sensor PQRSTA0 Zone controller ABZCA Electronic thermostat AQETC CTI Communication transfer interface PKFC0 CO2 Sensor PES C0RV0 Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWRC2 0 25m O Extension Wire PZCWR...

Страница 6: ...t Body kg lbs 8 5 18 7 8 5 18 7 Shipping kg lbs 11 3 24 9 11 3 24 9 Sound Pressure Levels H M L dB A 30 29 28 32 30 28 Sound Power Levels H M L dB A 54 53 52 54 53 52 Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications may be changed witho...

Страница 7: ...ght Body kg lbs 8 5 18 7 8 5 18 7 Shipping kg lbs 11 3 24 9 11 3 24 9 Sound Pressure Levels H M L dB A 34 32 28 37 34 30 Sound Power Levels H M L dB A 55 54 52 55 54 53 Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications may be changed wit...

Страница 8: ...Sound Power Levels H M L dB A 58 56 54 Power Supply Ø V Hz 1 220 240 50 1 220 60 Refrigerant Control EEV Transmission cable mm 1 0 1 5 2C Color White Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be considered for electrical work a...

Страница 9: ...16 5 8 16 5 8 Weight Body kg lbs 13 0 28 7 13 0 28 7 Shipping kg lbs 16 0 35 3 16 0 35 3 Sound Pressure Levels H M L dB A 43 39 34 46 41 34 Sound Power Levels H M L dB A 63 57 54 65 60 54 Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications...

Страница 10: ...16 6 35 6 16 6 35 6 Sound Pressure Levels H M L dB A 49 44 42 52 47 43 Sound Power Levels H M L dB A Power Supply Ø V Hz 1 220 240 50 1 220 240 50 1 220 60 1 220 60 Refrigerant Control EEV EEV Transmission cable mm 1 0 1 5 2C 1 0 1 5 2C Color White White Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicabl...

Страница 11: ...11 MULTI V Indoor Unit Wall Mounted Unit Standard 3 Dimensions SJ Chassis ARNU05GSJ 4 ARNU07GSJ 4 ARNU09GSJ 4 ARNU12GSJ 4 GGGGGGGGGGGGGGGGGGGARNU15GSJ 4 ...

Страница 12: ...MULTI V Indoor Unit 3 Dimensions 12 Wall Mounted Unit Standard SK Chassis ARNU18GSK 4 ARNU24GSK 4 ...

Страница 13: ...the installation manual in the product box 2 Unit shall be grounded in accordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit Note 3 2 1 Left rear piping Right rear piping 43 43 140 150 167 Unit Outline 167 Installation plate ...

Страница 14: ...Ø6 35 1 4 ARNU09GSJ 4 Ø12 7 1 2 Ø6 35 1 4 ARNU12GSJ 4 Ø12 7 1 2 Ø6 35 1 4 ARNU15GSJ 4 Ø12 7 1 2 Ø6 35 1 4 ARNU18GSK 4 Ø12 7 1 2 Ø6 35 1 4 ARNU24GSK 4 Ø15 88 5 8 Ø9 52 3 8 ARNU30GSVA4 Ø15 88 5 8 Ø9 52 3 8 ARNU36GSVA4 Ø15 88 5 8 Ø9 52 3 8 LOC Description Th1 Room thermistor Th2 Pipe in thermistor Th3 Pipe out thermistor Heat Exchanger C F F lndoor unit EEV Filter Filter Th3 Th2 Th1 Heating Cooling ...

Страница 15: ...indoor status CN DISP2 Display Display of indoor status CN EEV EEV output EEV control output CN U D Step motor Step motor output CN TH1 Room inlet pipe sensor Room and inlet pipe thermistor CN TH2 Outlet pipe sensor Outlet pipe thermistor CN REMO Remote controller Remote control line CN CC Dry contact Dry contact line CN EXT1 External On Off External On Off signal input CN LEAK Refrigerant leak de...

Страница 16: ... Display Display of indoor status CN EEV EEV output EEV control output CN U D Step motor Step motor output CN TH1 Room inlet pipe sensor Room and inlet pipe thermistor CN TH2 Outlet pipe sensor Outlet pipe thermistor CN REMO Remote controller Remote control line CN CC Dry contact Dry contact line CN EXT1 External On Off External On Off signal input CN LEAK Refrigerant leak detector Refrigerant lea...

Страница 17: ...oor CN DISP1 Display Display of indoor status CN DISP2 Display Display of indoor status CN LEV EEV output EEV control output CN U D Step motor Step motor output CN TH1 Room inlet pipe sensor Room and inlet pipe thermistor CN TH2 Outlet pipe sensor Outlet pipe thermistor CN REMO Remote controller Remote control line CN CC Dry contact Dry contact line CN EXT External On Off External On Off signal in...

Страница 18: ... 1 6 2 0 1 8 2 2 1 8 2 4 1 9 2 4 1 8 2 4 1 6 35 1 5 1 5 1 8 1 6 2 0 1 8 2 2 1 8 2 4 1 9 2 4 1 8 2 4 1 6 37 1 5 1 5 1 8 1 6 2 0 1 8 2 2 1 8 2 3 1 8 2 3 1 7 2 4 1 6 39 1 5 1 5 1 8 1 6 2 0 1 8 2 2 1 8 2 2 1 8 2 3 1 7 2 4 1 5 2 8 10 1 9 1 7 2 2 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 3 3 7 2 2 12 1 9 1 7 2 2 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 3 3 6 2 2 14 1 9 1 7 2 2 1 9 2 6 2 1 2 8 2 1 3 0 2 2 3 4 2 3 3 6 2...

Страница 19: ...4 5 3 6 5 2 3 9 5 6 4 0 5 7 3 9 5 8 3 7 6 0 3 4 7 1 10 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 3 5 3 12 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 2 5 3 14 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 1 5 2 16 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 9 0 5 1 18 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 8 8 5 1 20 4 8 4 1 5 7 4 5 6 6 4 9 7 1 5 0 7 6 5 2 8 5 5 4 8 ...

Страница 20: ... 7 9 12 9 7 4 20 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 5 7 9 12 7 7 3 21 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 5 7 9 12 7 7 3 23 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 5 7 9 12 5 7 1 25 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 3 7 7 12 3 7 0 27 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 12 0 7 6 12 2 7 0 29 7 0 6 0 8 3 6 6 9 7 7 1 10 4 7 3 11 1 7 6 11 9 7 4 12 0 6 9 31 7 0 6...

Страница 21: ...17 0 2 0 2 0 2 0 2 0 2 0 2 0 14 7 15 0 2 1 2 1 2 1 2 1 2 1 2 0 12 6 13 0 2 2 2 2 2 2 2 2 2 1 2 1 10 5 11 0 2 3 2 3 2 2 2 2 2 2 2 2 9 5 10 0 2 3 2 3 2 3 2 3 2 3 2 2 8 5 9 1 2 3 2 3 2 3 2 3 2 3 2 2 7 0 7 6 2 4 2 4 2 4 2 4 2 3 2 2 5 0 5 6 2 5 2 5 2 5 2 4 2 3 2 2 3 0 3 7 2 6 2 6 2 5 2 4 2 3 2 2 0 0 0 7 2 7 2 6 2 5 2 4 2 3 2 2 3 0 2 2 2 7 2 7 2 5 2 4 2 3 2 2 5 0 4 1 2 8 2 7 2 5 2 4 2 3 2 2 7 0 6 0 2 8 ...

Страница 22: ... 9 3 9 3 9 3 9 3 9 14 7 15 0 4 1 4 1 4 1 4 1 4 1 4 1 12 6 13 0 4 3 4 3 4 3 4 3 4 3 4 3 10 5 11 0 4 5 4 5 4 5 4 5 4 5 4 4 9 5 10 0 4 6 4 6 4 6 4 6 4 6 4 4 8 5 9 1 4 7 4 7 4 7 4 7 4 7 4 4 7 0 7 6 4 8 4 8 4 8 4 8 4 7 4 4 5 0 5 6 5 0 5 0 5 0 4 8 4 7 4 4 3 0 3 7 5 3 5 1 5 0 4 8 4 7 4 4 0 0 0 7 5 3 5 2 5 0 4 8 4 7 4 4 3 0 2 2 5 5 5 3 5 0 4 8 4 7 4 4 5 0 4 1 5 6 5 3 5 0 4 8 4 7 4 4 7 0 6 0 5 6 5 3 5 0 4 ...

Страница 23: ...8 7 8 7 8 7 7 12 6 13 0 8 1 8 1 8 1 8 1 8 1 8 1 10 5 11 0 8 5 8 5 8 5 8 5 8 5 8 2 9 5 10 0 8 7 8 7 8 6 8 6 8 6 8 2 8 5 9 1 8 8 8 8 8 8 8 8 8 8 8 2 7 0 7 6 9 1 9 1 9 1 9 0 8 8 8 2 5 0 5 6 9 4 9 4 9 4 9 1 8 8 8 2 3 0 3 7 9 9 9 6 9 4 9 1 8 8 8 2 0 0 0 7 10 1 9 7 9 4 9 1 8 8 8 2 3 0 2 2 10 3 10 0 9 4 9 1 8 8 8 2 5 0 4 1 10 5 10 0 9 4 9 1 8 8 8 2 7 0 6 0 10 6 10 0 9 4 9 1 8 8 8 2 9 0 7 9 10 6 10 0 9 4 ...

Страница 24: ...it continuous operation and performance can not be guaranteed When selecting the outdoor units avoid the air temperature range that is not guaranteed continuous operation 4 In accordance with operation limits of outdoor unit applicable range of capacity tables is different 5 Refer to Capacity tables and correction factor in the outdoor unit PDB for the actual performance data of each indoor unit a...

Страница 25: ...ure C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 0 3 0 5 1 0 2 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 0 3 0 3 0 3 0 5 0 5 1 0 1 0 Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 8 9m Vertical Louver Left Right Vertial L...

Страница 26: ...C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 9m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 12 6m 0 3...

Страница 27: ...emperature C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 9 2m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range...

Страница 28: ... C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 13 2m 0 3 ...

Страница 29: ...perature C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 9 6m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 1...

Страница 30: ...re C m 10 8 6 4 2 0 10 8 6 4 2 0 m m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 8m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 14m 0 ...

Страница 31: ...6 4 2 0 m m 0 3 0 5 1 0 1 5 24 26 28 m m 2 1 0 2 7 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 10m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 14 3m ...

Страница 32: ...m 2 1 0 2 7 0 3 0 5 1 0 1 5 0 5 0 3 30 32 26 28 2 1 0 2 7 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 13m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 14 3m 0 3...

Страница 33: ... 0 m m m m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 1 5 2 0 24 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 35 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 5m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 16 7m...

Страница 34: ...m m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 2 0 1 5 30 32 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 55 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 18m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 18 8m 0 3 0...

Страница 35: ... 8 6 4 2 0 m m m m 2 1 0 2 7 2 1 0 2 7 24 26 22 0 3 0 5 1 0 1 5 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 25 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 10 4m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 1...

Страница 36: ... 2 0 m m m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 1 5 30 32 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 45 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 6m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 18 2m ...

Страница 37: ... 6 4 2 0 m m m m 2 1 0 2 7 2 1 0 2 7 0 3 1 0 1 5 0 5 24 26 22 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 25 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 11 2m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 16 ...

Страница 38: ...m 2 1 0 2 7 2 1 0 2 7 0 3 0 5 1 0 1 5 0 5 0 3 30 32 26 28 26 28 Vertical Louver Center Vertial Louver angle 0 Top View Discharge angle 45 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s Vertical Louver Center Vertial Louver angle 0 Air speed 0 3m s Range 12 1m Vertical Louver Left Right Vertial Louver angle 50 Air speed 0 3m s Range 1...

Страница 39: ... s 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 28 28 30 30 32 28 0 5 0 5 0 5 0 5 1 5 2 5 2 5 1 5 0 5 1 0 Discharge angle 35 Cooling Temperature C Air velocity m s 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 2 7m 2m 1m 0m 8m 7m 6m 5m 4m 3m 2m 1m 0m 22 22 22 20 20 0 5 0 5 0 5 3 0 0 5 2 5 1 0 1 5 2 0 Discharge angle 25 Heating Temperature C Air velocity m s 2 7m 2m ...

Страница 40: ...A MFA kW FLA Cooling Heating ARNU05GSJ 4 SJ 50 220 240 Max 264 Min 198 0 31 15 0 030 0 25 30 0 30 0 ARNU07GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU09GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU12GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU15GSJ 4 SJ 0 31 15 0 030 0 25 30 0 30 0 ARNU18GSK 4 SK 0 65 15 0 058 0 52 53 0 53 0 ARNU24GSK 4 SK 0 65 15 0 058 0 52 53 0 53 0 ARNU30GSVA4 SV 1 19 15 0 113 0 95 88...

Страница 41: ... 4 34 32 28 ARNU12GSJ 4 37 34 30 ARNU15GSJ 4 42 39 32 ARNU18GSK 4 43 39 34 ARNU24GSK 4 46 41 34 ARNU30GSVA4 49 44 42 ARNU36GSVA4 52 47 43 ARNU05GSJ 4 ARNU07GSJ 4 ARNU09GSJ 4 1m 1m Microphone Measuring place Anechoic chamber 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 3...

Страница 42: ...000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC...

Страница 43: ...75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Cen...

Страница 44: ...80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz N...

Страница 45: ...ll should be solid enough to protect it from the vibration The place where the unit is not affected by an electrical noise The place where noise prevention is taken into consideration The place where the maintenance space for product is sufficient There should not be any heat source or steam near the unit Please read the instruction sheets completely before installing the product When the power co...

Страница 46: ... be done safely According to product type model line up sales region etc applicability of each chassis could be different According to product type model line up sales region etc applicability of each chassis could be different The lower left and the right side piping of Installation Plate According to product type model line up sales region etc applicability of each chassis could be different SJ ...

Страница 47: ...over ྙ ྚ 2 Remove the chassis cover from the unit 3 Pull back the tubing holder 4 Remove pipe port cover and positioning the tubing SV chassis 1 Open the panel of the indoor unit 2 Remove the chassis cover from the unit by loosing 5 screws 3 Pull back the tubing holder 4 Remove pipe port cover and position the piping SV chassis The feature can be changed according to type of model According to pro...

Страница 48: ...ping housing section Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause overflow from the drain pan through the inside of the unit CAUTION If the drain hose is routed inside the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors The feature can be changed accord...

Страница 49: ...t Seat the indoor unit on the installation plate 1 Hook the indoor unit onto the upper portion of the installation plate engage the three hooks at the top of the indoor unit with the upper edge of the installation plate Ensure that the hooks areproperly seated on the installation plate by moving it left and right 2 Unlock the tubing holder from the chassis and mount between the chassis and install...

Страница 50: ...it left and right 3 Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 4 Finish the assembly by screwing the unit to the installation plate by using two pieces of type C screws And assemble a chassis cover SJ SK chassis Recovery the chassis cover in Original place SV chassis The feature can be changed according to ...

Страница 51: ...pable of shutting down the power supply to the entire system must be installed CAUTION After the confirmation of the above conditions prepare the wiring as follows 1 Drill the piping hole with a ø 70mm hole core drill Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side 1 The drain hose should point downward for easy drain flow 2 Do not make dra...

Страница 52: ... of communication transmission cable put the 0 75mm2 cable or thinner cable on the clamp and tighten it with a plastic clamp to the other boss of the control panel In case that communication transmission cable is not needed to connect fix the other side of the clamp with a screw strongly WARNING Make sure that the screws of the terminal are fixed tightly The screw which fasten the wiring in the ca...

Страница 53: ...afts or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Uncontrolled areas such as an outside wall behind the remote controller This remote controller is equipped with a seven segment LED display For proper display of the remote controller LED s the remote controller should be installed properly The standard height ...

Отзывы: