40
MULTI V
Indoor Unit
Wall Mounted Unit (Standard)
8. Electric Characteristics
Symbols
MCA :
Minimum Circuit Amperes (A)
MFA :
Maximum Fuse Amperes (A)
kW :
Fan Motor Rated Output (kW)
FLA :
Full Load Amperes (A)
IFM :
Indoor Fan Motor
PI :
Maximum Power Input (W)
Note
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
the listed range limits.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA/MFA
MCA=1.25 x FLA
MFA
˺
4 x FLA
(Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.
Units
Power supply
IFM
PI
Model
Type
Hz
Volts
Voltage range
MCA
MFA
kW
FLA
Cooling
Heating
ARNU05GSJ*4
SJ
50
220-240
Max: 264
Min:198
0.31
15
0.030
0.25
30.0
30.0
ARNU07GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU09GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU12GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU15GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU18GSK*4
SK
0.65
15
0.058
0.52
53.0
53.0
ARNU24GSK*4
SK
0.65
15
0.058
0.52
53.0
53.0
ARNU30GSVA4
SV
1.19
15
0.113
0.95
88.0
88.0
ARNU36GSVA4
SV
1.19
15
0.113
0.95
105.0
105.0
ARNU05GSJ*4
SJ
60
220
Max: 242
Min:198
0.31
15
0.030
0.25
30.0
30.0
ARNU07GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU09GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU12GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU15GSJ*4
SJ
0.31
15
0.030
0.25
30.0
30.0
ARNU18GSK*4
SK
0.65
15
0.058
0.52
53.0
53.0
ARNU24GSK*4
SK
0.65
15
0.058
0.52
53.0
53.0
ARNU30GSVA4
SV
1.19
15
0.113
0.95
67.0
67.0
ARNU36GSVA4
SV
1.19
15
0.113
0.95
104.0
104.0