70
Multi V Ducted Indoor Units
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
WIRING
Vertical Air Handler NK Chassis
Table 37: NK Frame Wiring Diagram Legend.
Table 38: NK Frame DIP Switch Settings.
Terminal
Purpose
Function
CN-POWER
AC Power supply
AC Power line
CN-MOTOR1
Fan motor output
Motor output of BLDC
RV-VM
Sub PC power supply
Power supply connection
CN_OUT
Heater
Connection for heater
CN-FLOAT
Float switch input
Float switch sensing
CN-ZONE
Zone controller
Zone controller connection
CN-EEV
EEV Output
EEV control output
CN-OPTION
Optional PCB EPROM
Option PCB connection
CN-EXT
External ON / OFF controller
External ON / OFF controller connection
CN-DISPLAY
Display
Display of indoor status
CN-CC
Dry contact
Dry Contact connection
CN-PTC
Auxiliary heater
Auxiliary heater connection
CN-PIPE/OUT (RD)
Discharge pipe sensor
Pipe out thermistor
CN-LEAK (VI)
Refrigerant leak detector
Refrigerant leak detector connection
CN-PIPE/IN (WH)
Suction pipe sensor
Pipe in thermistor
CN-REMO (GN)
Wired remote controller
Wired remote control connection
CN-ROOM (YL)
Room sensor
Room air thermistor
CN-D/PUMP
Drain pump output
AC output for drain pump
CN-485
Communication
Connection between indoor and outdoor units
*For Gen 4 Multi V vertical air handler indoor units, DIP switches 1, 2, 7 and 8 must be set to OFF. These DIP switches are
used for other models.
**To enable Generation 4 features, outdoor unit DIP Switch No. 3 must be set to ON. Please refer to the Multi V IV, Multi V Wa-
ter IV, Multi V S Engineering Manual for additional information.
DIP Switch Setting
Off
On
Remarks
SW3
GROUP CONTROL
Master
Slave
Group control setting using 7-Day Programmable Controller; selects Master /
Slave on each indoor unit
SW4
DRY CONTACT
MODE
Variable
Auto
Sets operation mode for optional Dry Contact accessory
1. Variable: Auto or Manual Mode can be set through 7-Day Programmable
Controller or Wireless Remote Controller (factory default setting is Auto if
there is no setting)
2. Auto: For Dry Contact, it is always Auto mode
SW5
CONTINUOUS FAN
Off
On
Selects continuous fan for ducted indoor units.
1. On: Indoor unit fan will always operate at a set fan speed, except when
the system is off, or the outdoor unit is in defrost mode (when the oudoor unit
is in defrost mode, the fan will operate at super low fan speed)
2. Off: Indoor unit fan speed can be changed by on / off
SW6
HEATER INTERLOCK
Off
On
Selects heater interlock function for vertical air handler units
1. On: Automatic (heater will automatically operate during heating mode)
2. Off: Manual (heater needs to be manually turned on during heating mode)