20
Multi V Ducted Indoor Units
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
1
Power Input is rated at high speed.
2
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or
destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F)
under section 608 of CAA.
3
All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and
must comply with applicable local and national codes. Ensure the communication cable
is properly grounded at the master outdoor unit only. Do not ground the ODU−IDU com
-
munications cable at any other point.
EEV: Electronic Expansion Valve
Power wiring is field supplied and must comply with the applicable local and national
codes. Power Supply (V/Hz/Ø): 208-230/60/1
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft
level difference between outdoor and indoor units. All capacities are net with a combina-
tion ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and
67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Table 8:
Vertical Air Handler NJ Chassis IDU Specifications
Model No.
ARNU123NJA4
ARNU183NJA4
ARNU243NJA4
ARNU303NJA4
ARNU363NJA4
Cooling Mode Performance
Capacity (Btu/h)
12,000
18,000
24,000
30,000
36,000
Power Input
1
(W)
80
80
120
178
228
Heating Mode Performance
Capacity (Btu/h)
13,500
20,000
27,000
34,000
40,000
Power Input
1
(W)
80
80
120
178
228
Entering Mixed Air
Cooling Max. (°F WB)
76
76
76
76
76
Heating Min. (°F DB)
59
59
59
59
59
Unit Data
Refrigerant Type
2
R410A
R410A
R410A
R410A
R410A
Refrigerant Control
EEV
EEV
EEV
EEV
EEV
Net Unit Weight (lbs.)
117
117
117
117
121
Shipping Weight (lbs.)
140
140
140
140
144
Communication Cable
4
(No. x AWG)
2 x 18
2 x 18
2 x 18
2 x 18
2 x 18
Fan
Type
Sirocco
Sirocco
Sirocco
Sirocco
Sirocco
Motor
1
1
1
1
1
Housing
1
1
1
1
1
Motor/Drive
Brushless Digitally Controlled / Direct
Airflow Rate H/M/L (CFM)
Standard Mode
530 / 480 / 380
580 / 530 / 480
710 / 640 / 480
880 / 800 / 630
990 / 880 / 800
Airflow Rate H/M/L (CFM)
High Mode (Factory Set)
530 / 480 / 380
580 / 530 / 480
710 / 640 / 480
880 / 800 / 630
990 / 880 / 800
External Static Pressure (in. wg)
Standard Mode
0.3
0.3
0.3
0.3
0.3
External Static Pressure (in. wg)
High Mode (Factory Set)
0.5
0.5
0.5
0.5
0.5
Piping
Liquid Line (in., O.D.)
1/4 Flare
1/4 Flare
3/8 Flare
3/8 Flare
3/8 Flare
Vapor Line (in., O.D.)
1/2 Flare
1/2 Flare
5/8 Flare
5/8 Flare
5/8 Flare
Condensate Line (in., I.D.)
1
1
1
1
1
GENERAL DATA
Specifications
−
Vertical Air Handler NJ Chassis