5. Trouble Shooting
6.6 Check code Trouble shooting CH01, CH02, CH06
Ω
10k
Ω
Unplugged
Plugged
Check the resistance
Check the voltage
V
2.5Vdc
Unplug the sensor
on Indoor unit PCB
Estimate the Voltage
of each sensor.
Is the voltage of
the sensor 2.5Vdc
at 25˚C
Repair or Change the PCB.
Check the
Connector connection
Is it normal ?
Estimate the resistance
of each sensor.
Plug the sensor
on Indoor unit PCB
Is the resistance of
the sensor 10
Ω
/
5k
Ω
at 25˚C?
Yes
Yes
No
Correct connection
Yes
No
Correct connection
No
Correct connection
Check Flow Chart
01
02
06
Indoor air sensor
Indoor inlet pipe sensor
Indoor outlet pipe sensor
• Connector connection error
• Faulty PCB
• Faulty sensor (Open / Short)
• Connector connection error
• Faulty PCB
• Faulty sensor (Open / Short)
• Connector connection error
• Faulty PCB
• Faulty sensor (Open / Short)
Normal resistor : 10K
Ω
/ at 25˚C (Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
Normal resistor : 5K
Ω
/ at 25˚C(Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
Normal resistor : 5K
Ω
/ at 25˚C(Unplugged)
Normal voltage : 2.5Vdc / at 25˚C(Plugged)
Refer to sensor resistance table.
Display
code
Title
Cause of error
Check point & Normal condition