APPLICATIOn GUIDeLIneS
Art Cool Premier W
all Mounted Engineering Manual
Cooling / heating Correction Factors
For the Art Cool Premier system,
calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, determine
the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction factors
as shown in Figure 5 and Figure 6. Multiply the correction factors by the cooling or heating capacity obtained from the capacity table using
design conditions. The resultant is the nET cooling or heating capacity.
EQuiPMEnt SElECtion ProCEdurE
Component
Size (Inches)
1/4
3/8
1/2
5/8
3/4
7/8
1
1-1/8 1-1/4 1-3/8 1-1/2 1-5/8 1-3/4 2-1/8
Elbow (ft.)
0.5
0.6
0.7
0.8
1.2
1.3
1.5
1.6
1.8
2.0
2.1
2.3
2.5
2.8
Equivalent Piping length for Piping Components
Table 10: Equivalent Piping Length for Elbows
Cooling
9k,12k
65.6
98.4
Total Pipe Length (ft)
Capacity (%)
100
90
95
24.6
capacity coefficient Factors
Figure 5:
Cooling Capacity Coefficient Factor
Figure 6:
Heating Capacity Coefficient Factor
Heating
Capacity (%)
24.6
100
95
9k,12k
65.6
98.4
Total Pipe Length (ft)