Due to our policy of continuous product innovation, some specifications may change without notification.
Due to our policy of continuous product innovation, some specifications may change without notification.
reFrIGerAnT deSIGn | 53
Refrigerant Piping Design & Layout Best Practices
ElECtriCal ConnECtionS
Air
Conditioner
Main Power Source
Circuit Breaker
Use a circuit breaker
Or time delay fuse
Always use a circuit breaker or time delay fuse when connect-
ing electrical wiring to the unit.
outdoor Electrical Connection
•
Comply with local codes while running wire from the
indoor unit to the outdoor unit.
•
Be sure to connect wire firmly.
•
Separately wire the high and low voltage lines.
•
Use heat-proof electrical wiring capable of withstand-
ing temperatures up to 167
°
F.
•
Use outdoor and waterproof connection cable
rated up to 300V for the connection between
indoor and outdoor unit.
•
Do not allow wire to touch refrigerant tubing, the com-
pressor or any moving parts.
Figure 30:outdoor Unit Connection
1. Remove the control cover from the unit by
loosening the fastening screw (Figure 30).
2. Take off the caps on the conduit panel.
3. Connect both the power supply and low voltage
lines to the corresponding terminals on the ter-
minal block (see Figure 32 and Figure 33).
4. Be sure to ground the unit by following local
codes (see Figure 31).
5. Allow for enough length (add several inches)
for each wiring.
6. Secure the cable with the cord clamp.
7. Secure conduit tubes with lock nuts.
8. Refix the control cover to the original position
with the fastening screw.
Terminal block
Connecting
cable
Power
supply
cord
Conduit panel
Tubing cover
Over 0.2”
Art Cool Mirror
Outdoor Unit
208/230 VA C
Figure 31:Circuit Breaker
Figure 32:Terminal Block Wiring Diagram LAU090HSV2, LAU120HSV2
Figure 33:Terminal Block Wiring Diagram LAU180HSV2, LAU240HSV2