44 | APPLICATIon GuIdeLIneS
Art Cool Mirror W
all Mounted Engineering Manual
Outdoor Installation
PlaCEMEnt ConSidErationS
Proper airflow through the oDU coil is critical for proper unit operation. When installing the oDU, consider service, inlet, and outlet, and
minimum allowable space requirements as illustrated in the diagrams below.
Specific clearance requirements in the diagrams below are for the Art Cool Mirror oDU. Figure 15 shows the overall minimum clearance that
must be observed for safe operation and adequate airflow around the oDU. If placing the unit close to a retaining wall or building; see Figure
16, for proper placement and adequate clearance space from the side and rear of the oDU..
Figure 15: Art Cool Mirror outdoor Unit Clearance
Single Zone art Cool Mirror Wall Mount outdoor unit Clearance
Outdoor Unit Clearance
Figure 16: Art Cool Mirror outdoor Unit next to Wall - Clearance
Outdoor Unit
Wall Clearance
Sunroof
Overhang
Or Roof
Figure 17: Art Cool Mirror outdoor Unit Under Roof/overhang
When placing the outdoor unit under an overhang, awning, sunroof
or other "roof-like" structure, be sure to observe the clearance for
height in relation to the unit as shown in Figure 17. This clearance
ensures that heat radiation from the condenser is not restricted
around the unit.
Adhere to all clearance requirements if installing the unit on a roof.
Be sure to level the unit and ensure that unit is adequately an-
chored. Consult local codes regarding rooftop mounting.
Do not place the unit where animals and/or plants will be in the path of
the warm air; or where the warm air and/or noise will disturb neighbors.