reFrIGerAnT deSIGn | 49
Refrigerant Piping Design & Layout Best Practices
inStallation & layout bESt PraCtiCES
Refrigerant Piping System Layout
no Pipe Size Substitutions
Using a different size is prohibited and may result in a system malfunction or failure to work at all.
in-line refrigeration Components
Components such as oil traps, solenoid valves, filter-dryers, sight glasses, tee fittings, and other after-market accessories are not permitted
on the refrigerant piping system between the outdoor unit and the indoor unit. Art Cool Mirror Wall Mount air-source systems are provided
with redundant systems that assure oil is properly returned to the compressor. Sight-glasses and solenoid valves may cause vapor to form
in the liquid stream. over time, dryers may deteriorate and introduce debris into the system. The designer and installer verify the refrigerant
piping system is free of traps, sagging pipes, sight glasses, filter dryers, etc.
Pipe Supports
A properly installed pipe system should be adequately supported
to avoid pipe sagging. Sagging pipes become oil traps that lead to
equipment malfunction.
Pipe supports should never touch the pipe wall; supports shall be
installed outside (around) the primary pipe insulation jacket (see
Figure 21). Insulate the pipe first because pipe supports shall be
installed outside (around) the primary pipe insulation jacket. Clevis
hangers should be used with shields between the hangers and
insulation. Field provided pipe supports should be designed to
meet local codes. If allowed by code, use fiber straps or split-ring
hangers suspended from the ceiling on all-thread rods (fiber straps
or split ring hangers can be used as long as they do not compress
the pipe insulation). Place a second layer of insulation over the pipe
insulation jacket to prevent chafing and compression of the primary
insulation within the confines of the support pipe clamp.
A properly installed pipe system will have sufficient supports to avoid
pipes from sagging during the life of the system. As necessary,
place supports closer for segments where potential sagging could
occur. Maximum spacing of pipe supports shall meet local codes.
If local codes do not specify pipe support spacing, pipe shall be
supported:
• Maximum of five feet (5′) on center for straight segments of pipe up
to 3/4" outside diameter size.
Wherever the pipe changes direction, place a hanger within twelve
(12) inches on one side and within twelve to nineteen (12 to 19)
inches of the bend on the other side as shown in Figure 22.
Figure 21: Pipe Hanger Details
Figure 22: Typical Pipe Support
Location—Change in Pipe Direction
Figure 23: Pipe Support at
Indoor Unit
Max. 12"
~ 12" – 19"
A
B
A + B ~ 12" – 19"