Piping and Wiring for Outdoor Unit
Wiring Procedure for Power Cable and Connecting Cable
Step 1.
: Disassemble the side panel from the outdoor unit by loosing screws.
Step 2.
: Connect Power cable to Main Power Terminal and Connecting cable to Control
Terminal, respectively.
See below figure for detailed information. When connecting earth cable, the
diameter of cable should be bigger than 1.6mm
2
to secure safety. The earth cable is
connected to the terminal block where earth symbol is marked.
Step 3.
: Use cable clamps (or cord clamps) to prevent unintended move of Power cable and
Connecting cable.
Step 4.
: Reassemble the side panel to the outdoor unit by fastening screws.
Circuit Breaker Specification
• Select a power source that is capable of supplying the current required by the AWHP.
• Use a recognized circuit breaker between the power source and the unit.
A disconnection device to adequately disconnect all supply lines must be fitted.
• Capacity of circuit breaker recommended.
• Separate main power supply and heater supply.
Notes:
1. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
2. Select wire spec. based on the MCA
3. Recommended circuit breaker is ELCB (Earth Leakage Circuit breaker)
4. RLA is measured during each individual compressor test condition.
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating Over current Protective device
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
S/Heater: Sanitary Water Tan Heater
Circuit
Breaker(A)
MOP
(A)
Circuit
Breaker(A)
MOP
(A)
Circuit
Breaker(A)
MOP
(A)
FLA
(A)
Capacity
(kW)
RLA
(A)
Capacity
(kW)
Outdoor
Power
Supply
Power
Supply
Power
Supply
Indoor
For Electric Heater
(with S/Heater)
For Electric Heater
(without S/Heater)
For Heat Pump
Sanitary Tank Heater
Electric Heater
Compressor
RLA
(A)
FLA
(A)
MOP & Circuit Breaker
Core Component Electrical Spec.
Model
3
12.5
1Ø
230V
AHUW096A0
AHUW096A1
AHUW126A0
AHUW146A0
AHUW166A0
AHUW096AN
AHUW168A1
AHUW148A1
AHUW128A1
9.7
17.0
17.0
17.0
9.7
5.3
5.0
4.0
15
25
27
27
15
9.9
2+2
3+3
2+2+2
3+3
2+2+2
3+3
2+2+2
3+3
2+2+2
1Ø 230V
3Ø 220V
3Ø 400V
1Ø 230V
3Ø 220V
3Ø 400V
1Ø 230V
3Ø 220V
3Ø 400V
1Ø 230V
3Ø 220V
3Ø 400V
8.3
12.5
15.8
8.7
12.5
15.8
8.7
12.5
15.8
8.7
12.5
15.8
8.7
23.9
40.3
23.9
14.0
13.3
11.1
20
40
20
13
13
10
27
41
37
22
41
37
22
41
37
22
41
37
22
30
40
30
20
40
30
20
40
30
20
40
30
20
45
53
49
38
53
49
38
53
49
38
53
49
38
40
50
40
30
50
40
30
50
40
30
50
40
30
1~
220-240V
50Hz
3N~
380-415V
50Hz
1~
220-240V
50Hz
1~
220-240V
50Hz
25
27
27
17.0
9.7
15
3+3
2+2
1Ø 230V
1Ø 230V
8.3
12.5
40.3
23.9
40
20
41
27
30
45
40
40
53
50
AHNW096A0
AHNW09604A1
AHNW126A0
AHNW146A0
AHNW166A0
AHNW09606A0
AHNW09A06A0
AHNW09806A0
AHNW16606A1
AHNW16A06A1
AHNW16806A1
AHNW16606A1
AHNW16A06A1
AHNW16806A1
AHNW16606A1
AHNW16A06A1
AHNW16806A1
AHNW16606A1
AHNW16606A1
AHNW16606A1
AHNW09604A1
AHNW16606A1
AHNW16A06A1
AHNW16806A1
AHNW16606A1
AHNW16A06A1
AHNW16806A1
AHUW126A1
AHUW146A1
ㅤ
AHUW166A1
ㅤ
AHUW096A2
1~
220-240V
50Hz
1~
220-240V
50Hz
29
14.5
16.9
3+3
2+2+2
3+3
2+2+2
1Ø 230V
3Ø 220V
3Ø 400V
1Ø 230V
3Ø 220V
3Ø 400V
12.5
15.8
8.7
12.5
15.8
8.7
34.7
40.1
40
30
41
37
22
41
37
22
40
30
20
40
30
20
53
49
38
53
49
38
50
40
30
50
40
30
AHUW126A2
AHUW146A2
ENGLISH