System Set-Up
22
Function
Description
Value #1
Note
-
-
-
-
Default
16
°
C
Range
16~25
°
C
Value #2
Note
Default
00
Range
23
Function
Description
Function
Description
Value #1
Note
Default
-10
°
C
Range
-20~05
°
C
Value #2
Note
Default
15
°
C
Range
10~20
°
C
24
Value #1
Note
Default
21
°
C
Range
20~30
°
C
Value #2
Note
Default
16
°
C
Range
16~19
°
C
25
Function
Description
Value #1
Note
Default
55
°
C
Range
35~55
°
C
Value #2
Note
Default
15
°
C ( * 20
°
C)
Range
15~34
°
C ( * 20~34
°
C)
26
Function
Description
Value #1
Note
Default
00
Range
00~01
Sanitary water
heating should be
* : Electric heater is
not
used.
enable
• If sanitary water
heating is disable,
Code
Item
Setting Cut-off Temperature in Cooling Mode
(FCU setting included)
Determine leaving water temperature when the product is turned off.
This function is used for preventing condensation
on the floor in cooling mode.
Cut-off temperature. Value #1 is valid when Value #2 is
'01 (that means, FCU is installed)'."
Determines if FCU is installed or not. '01' means 'FCU is
NOT installed', and '00' means 'FCU is installed.'
00(Equipped)~01(NOT Equipped)
Setting outdoor temperature range for Weather-dependent
operation
Setting outdoor Max/Min temperature for weather-dependent
operation
Upper Limit of setting range
Lower Limit of setting range
Setting indoor air temperature range for Weather-dependent
operation
Setting indoor Max/Min temperature for weather-dependent
operation
Upper Limit of setting range
Lower Limit of setting range
Setting leaving water temperature range for Weather-dependent operation
Setting leaving water Max/Min temperature for
weather-dependent operation
Upper Limit of setting range
Lower Limit of setting range
Setting Disinfection Operation
Setting start/maintain time for disinfection
Enable/Disable of Disinfection Operation(00:Disable , 01:Enable)
Detail
Remark
78
Air-to-Water Heat Pump