2. Specifications
5
MULTI
Outdoor Unit
Multiple piping type
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Power factor could vary less than ±1% according to the operating conditions.
4. Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Sound power level is measured on the rated condition in the reverberation rooms by ISO 3741 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
5. Performances are based on the following conditions :
• *Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• *Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
6. This product contains Fluorinated greenhouse gases.
Model Names
A3UW21GFAC
Combination
Sum of Indoor Units Capacity
kBtu/h
30
Number of Indoor Units
EA
3
Number of BD Units
EA
-
Cooling Capacity*
Min.~Rated~Max.
kW
1.23 ~ 6.15 ~ 7.03
Min.~Rated~Max.
Btu/h
4,200 ~ 21,000 ~ 24,000
Heating Capacity*
Min.~Rated~Max.
kW
1.48 ~ 6.15 ~ 7.03
Min.~Rated~Max.
Btu/h
5,040 ~ 21,000 ~ 24,000
Power Input
Cooling*
Min.~Rated~Max.
kW
0.31 ~ 1.66 ~ 2.55
Heating*
Min.~Rated~Max.
kW
0.36 ~ 1.54 ~ 2.61
Power Supply
V , Ø , Hz
220, 1, 60
Running Current
Cooling*
Min.~Rated~Max.
A
1.1 ~ 7.5 ~ 11.5
Heating*
Min.~Rated~Max.
A
1.1 ~ 7.0 ~ 11.8
Power Factor
Rated
-
0.94
Power Supply Cable (included Earth)
No. × mm²
3C × 2.5
Casing Color
-
Warm Gray
Dimensions
W × H × D
mm
770 × 545 × 288
Net Weight
kg (lbs)
36.7 (80.9)
Shipping Weight
kg (lbs)
39.5 (87.1)
Compressor
Type
-
Twin Rotary
Model
Model × No.
GAT156MA × 1
Motor type
-
BLDC
Motor Output
W × No.
1,500 (at 60Hz) × 1
Refrigerant
Type
-
R410A
GWP (Global Warming Potential)
-
2087.5
Precharged Amount
g (oz)
1,450 (51.2)
t-CO
₂
eq.
-
3.027
Control
-
Electronic Expansion Valve
Chargeless-Pipe Length
m (ft)
30 (98.4)
Additional Charging Volume
g/m (oz/ft)
20 (0.22)
Refrigerant Oil
Type
-
RB68A
Charged volume
cc × No.
400 × 1
Heat Exchanger
(Row×Column×Fins per inch) × No.
-
(2 × 24 × 14) × 1
Fan
Type
-
Propeller
Air Flow Rate
m³/min × No.
28.2 × 1
Fan Motor
Type
-
BLDC
Output
W × No.
43 x 1
Sound Pressure Level
Cooling
Rated
dB(A)
49
Heating
Rated
dB(A)
52
Sound Power Level
Cooling
Max.
dB(A)
64
Piping Connections
Liquid
Outer Dia. × No.
mm(inch)
Ø 6.35(1/4) × 3
Gas
Outer Dia. × No.
mm(inch)
Ø 9.52(3/8) × 3
Piping Length
Total Piping
Max.
m (ft)
40 (131.2)
Main Piping
Standard
m (ft)
-
Max.
m (ft)
-
Total Branch
Max.
m (ft)
-
Each Branch
Standard
m (ft)
7.5 (24.6)
Max.
m (ft)
20 (65.6)
Maximum Height
Difference
ODU~IDU
Max.
m (ft)
15 (49.2)
IDU~IDU
Max.
m (ft)
7.5 (24.6)
Operation Range
(Outdoor Temperature)
Cooling
Min. ~ Max.
ºC(ºF)DB
-5 (23.0) ~ 48 (118.4)
Heating
Min. ~ Max.
ºC(ºF)WB
-10 (14.0) ~ 18 (64.4)
Содержание A2UW18GFAC