130
MULTI
Outdoor Unit
Multiple piping type
6. Capacity Correction Factor
■
Rate of change in capacity due to the branch piping length
Acoording to line up of each region, availability of indoor units may vary.
7k Btu/h (2.1 kW) or less models
9k Btu/h (2.5 kW) models
12k Btu/h (3.5 kW) models
18k Btu/h (5.0 kW) models
24k Btu/h (7.1 kW) models
Piping length(m)
Rate of change in capacity
Cooling(%)
Heating(%)
7.5
100.0
100.0
10
98.4
99.2
15
95.8
97.8
20
93.2
96.4
25
90.6
95.0
Piping length(m)
Rate of change in capacity
Cooling(%)
Heating(%)
7.5
100.0
100.0
10
98.0
99.0
15
94.8
97.4
20
91.6
95.8
25
88.4
94.2
Piping length(m)
Rate of change in capacity
Cooling(%)
Heating(%)
7.5
100.0
100.0
10
97.6
98.6
15
93.8
96.4
20
89.9
94.1
25
86.1
91.9
Piping length(m)
Rate of change in capacity
Cooling(%)
Heating(%)
7.5
100.0
100.0
10
98.6
99.6
15
96.4
99.0
20
94.1
98.3
25
91.9
97.7
Piping length(m)
Rate of change in capacity
Cooling(%)
Heating(%)
7.5
100.0
100.0
10
98.2
99.2
15
95.4
98.0
20
92.4
96.6
25
89.6
95.4