212
Multi type Air Conditioner
(3-way) Valve
(3) Gas Charging
(After Evacuation)
• Procedure
1. Connect the gauge to the charging cylinder.
- Connect the charge hose which you disconnect-
ed from the vacuum pump to the valve at the
bottom of the cylinder.
- If you are using a gas cylinder, also use a scale
and reverse the cylinder so that the system can
be charged with liquid.
2. Purge the air from the charge hose.
- Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge
the air. (Be careful of the liquid refrigerant). The
procedure is the same if using a gas cylinder.
3. Open the low handle on the gauge and charge
the system with liquid refrigerant.
- If the system can not be charged with the speci-
fied amount of refrigerant, it can be charged
with a little at a time (approximately 150g each
time) while operating the air conditioner in the
cooling cycle; however, one time is not suffi-
cient, wait approximately 1 minute and then
repeat the procedure(pumping down-pin).
4. Immediately disconnect the charge hose from
the gas side valve's service port.
- Stopping partway will allow the gas to be dis-
charged.
- If the system has been charged with liquid
refrigerant while operating the air conditioner
turn off the air conditioner before disconnecting
the hose.
5. Mount the valve stem nuts and the service port
nut.
- Use torque wrench to tighten the service port
nut to a torque of 1.8 kg.m.(4.2kg.m/5.5kg.m.)
- Be sure to check for gas leakage.
manifold gauge
Charging
cylinder
Hi- handle
(OPEN)
Low-handle
(OPEN)
Check valve
Indoor unit
Outdoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
Indoor unit
Liquid side
Open
Gas side
2-Way
valve
Open
3-Way
valve
This is different from previous procedures.
Because you are charging with liquid refrigerant
from the gas side, absolutely do not attempt to
charge with larger amounts of liquid refrigerant
while operating the air conditioner.
Содержание A2UW146FA0
Страница 143: ...Service Manual 143 Schematic Diagram 2 Art Cool Type ...
Страница 144: ...144 Multi type Air Conditioner Schematic Diagram 3 Art Cool Deluxe Type A C MOTOR ...
Страница 145: ...Service Manual 145 Schematic Diagram 3 Art Cool Deluxe Type BLDC MOTOR ...
Страница 147: ...Service Manual 147 Schematic Diagram SLIM DUCT B1 B2 ...
Страница 157: ...Service Manual 157 Schematic Diagram 15 SLIM DUCT B1 B2 ...
Страница 161: ...Service Manual 161 Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Страница 163: ...Service Manual 163 Schematic Diagram TOP VIEW BOTTOM VIEW 3 Art Cool Deluxe Type BLDC MOTOR ...
Страница 164: ...164 Multi type Air Conditioner Schematic Diagram 4 Duct Type High static BH BG chassis Built in type BP chassis ...
Страница 165: ...Service Manual 165 Schematic Diagram Low static BT BT1 chassis ...
Страница 166: ...166 Multi type Air Conditioner Schematic Diagram TOP VIEW BOTTOM VIEW Low static B1 B2 ...
Страница 167: ...Service Manual 167 Schematic Diagram 5 Casset Type 1 way TC Chasis ...
Страница 168: ...168 Multi type Air Conditioner Schematic Diagram 1 way TC1 Chasis TOP VIEW BOTTOM VIEW ...
Страница 169: ...Service Manual 169 Schematic Diagram 4 way TE TF TD chassis 4 way TE1 TH chassis TOP VIEW BOTOM VIEW 58 B ...
Страница 171: ...Service Manual 171 Schematic Diagram VB chassis ...
Страница 172: ...172 Multi type Air Conditioner Schematic Diagram VB chassis TOP VIEW BOTOM VIEW ...
Страница 175: ...Service Manual 175 Schematic Diagram 3 Outdoor Unit 1 Component side ...
Страница 176: ...176 Multi type Air Conditioner Schematic Diagram 2 Solder side ...
Страница 177: ...Service Manual 177 Schematic Diagram 3 Central control PCB 2 Bottom View 1 Top View ...
Страница 178: ...178 Multi type Air Conditioner 4 SUB P W B ASSEMBLY 1 Art Cool Type TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 268: ...P No 3828A20097W April 2006 Printed in Korea ...