Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: near the rated
current
Temp. difference
: over 8°C
Temp. Difference
Operating Current
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal value)
High
Defective compressor
Current is low.
Normal
Excessive amount of
High pressure does not quickly
refrigerant
rise at the beginning of operation.
Insufficient amount of
Current is low.
Lower
Higher
refrigerant(Leakage)
Clogging
Higher
Cycle Troubleshooting Guide
Содержание A2UW146FA0
Страница 143: ...Service Manual 143 Schematic Diagram 2 Art Cool Type ...
Страница 144: ...144 Multi type Air Conditioner Schematic Diagram 3 Art Cool Deluxe Type A C MOTOR ...
Страница 145: ...Service Manual 145 Schematic Diagram 3 Art Cool Deluxe Type BLDC MOTOR ...
Страница 147: ...Service Manual 147 Schematic Diagram SLIM DUCT B1 B2 ...
Страница 157: ...Service Manual 157 Schematic Diagram 15 SLIM DUCT B1 B2 ...
Страница 161: ...Service Manual 161 Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Страница 163: ...Service Manual 163 Schematic Diagram TOP VIEW BOTTOM VIEW 3 Art Cool Deluxe Type BLDC MOTOR ...
Страница 164: ...164 Multi type Air Conditioner Schematic Diagram 4 Duct Type High static BH BG chassis Built in type BP chassis ...
Страница 165: ...Service Manual 165 Schematic Diagram Low static BT BT1 chassis ...
Страница 166: ...166 Multi type Air Conditioner Schematic Diagram TOP VIEW BOTTOM VIEW Low static B1 B2 ...
Страница 167: ...Service Manual 167 Schematic Diagram 5 Casset Type 1 way TC Chasis ...
Страница 168: ...168 Multi type Air Conditioner Schematic Diagram 1 way TC1 Chasis TOP VIEW BOTTOM VIEW ...
Страница 169: ...Service Manual 169 Schematic Diagram 4 way TE TF TD chassis 4 way TE1 TH chassis TOP VIEW BOTOM VIEW 58 B ...
Страница 171: ...Service Manual 171 Schematic Diagram VB chassis ...
Страница 172: ...172 Multi type Air Conditioner Schematic Diagram VB chassis TOP VIEW BOTOM VIEW ...
Страница 175: ...Service Manual 175 Schematic Diagram 3 Outdoor Unit 1 Component side ...
Страница 176: ...176 Multi type Air Conditioner Schematic Diagram 2 Solder side ...
Страница 177: ...Service Manual 177 Schematic Diagram 3 Central control PCB 2 Bottom View 1 Top View ...
Страница 178: ...178 Multi type Air Conditioner 4 SUB P W B ASSEMBLY 1 Art Cool Type TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 268: ...P No 3828A20097W April 2006 Printed in Korea ...