When compressor does not operate normally.
■
Communication error between Indoor and Outdoor (Error Code
)
Trouble 7-1
Does the operating LED in display PCB
Ass'y blink 5 times?
• Check the state of connecting cable
(4 line) bewteen indoor and outdoor unit .
NO
YES
Is the connecting state of connector out-
door PCB Ass'y right.
• Electrical wiring diagram(Colors)
• Check the connecting state
of connectors in outdoor PCB Ass'y
(CN_Data - Terminal Block.)
NO
YES
Is the connection of CN-DATA between
indoor and outdoor unit right?
Replace the PCB Ass'y.
• Main PCB Ass'y (Indoor/Outdoor)
• Reconnect the cable to terminal block.
• Check the PCB pattern(Resoldering).
NO
YES
Содержание A2UN186FA0
Страница 104: ... 104 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Страница 105: ... 105 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Страница 106: ... 106 3 Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Страница 107: ... 107 4 Convertible Type Indoor Unit ...
Страница 108: ... 108 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Страница 109: ... 109 6 SUB P W B ASSEMBLY Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Страница 110: ... 110 7 Outdoor Unit MAIN P C B ASM V P U N W ...
Страница 111: ... 111 Schematic Diagram 1 Room Type Indoor Unit ...
Страница 113: ... 113 3 Art Cool Type Indoor Unit ...
Страница 114: ... 114 4 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Страница 120: ... 120 354212 249951 268714 266012 352114 263230 352118 330870 158591 3 Cassette Type Indoor Unit AMNN126EA0 AMNN186TEA0 ...
Страница 121: ... 121 346810 130411 359011 152312 135802 135312 2 W0CZZ 137211 267110 352150 352150 130911 140570 268712 146811 ...
Страница 132: ...P No 3828A20097N August 2003 Printed in Korea ...