- 60 -
(5) Connecting Pipings and the cable to Outdoor unit
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be
guided by the circuit diagram pasted on the inside of control box cover.
2) The means for disconnection from a power supply shall be incorporated in the fixed wiring and have
an air gap contact separation of at least 3mm in each active(phase) conductors.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source.
5) Confirm that electrical capacity is sufficient.
6) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal
function of a overload protection device.
• Proper starting power is not given to the compressor.
1) Connecting the pipings to the Outdoor unit
1. When piping installation work you must be used the
connector.
2. Align the center of the pipings and sufficiently tight-
en the flare nut by hand
3. Finally, tighten the flare nut with torque wrench until
the wrench clicks.
■
When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
*Connecting pipe size
Indoor Units
Gas
Liquid
A
B
A
B
12K
18K
Ø9.52
→
Ø12.7
Not necessary
24K
Indoor Units
Gas side
Liquid side
7K
Ø9.52(3/8)
Ø6.35(1/4)
9K
Ø9.52(3/8)
Ø6.35(1/4)
12K
Ø12.7(1/2)
Ø6.35(1/4)
18K
Ø12.7(1/2)
Ø6.35(1/4)
24K
Ø12.7(1/2)
Ø6.35(1/4)
A
B
Connector
Gas side piping
Torque
wrench
Outdoor unit
Liquid side piping
Connector
A-UNIT
B-UNIT
C-UNIT
Содержание A2UN186FA0
Страница 104: ... 104 Electronic Control Device 1 Room Type Indoor Unit MAIN P C B DC ASM MAIN P C B AC ASM ...
Страница 105: ... 105 2 Cassette Type Indoor Unit MAIN P C B DC ASM ...
Страница 106: ... 106 3 Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Страница 107: ... 107 4 Convertible Type Indoor Unit ...
Страница 108: ... 108 5 Display ASSY Room Type Indoor Unit Convertible Type Indoor Unit Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Страница 109: ... 109 6 SUB P W B ASSEMBLY Art Cool Type Indoor Unit TOP VIEW BOTTOM VIEW ...
Страница 110: ... 110 7 Outdoor Unit MAIN P C B ASM V P U N W ...
Страница 111: ... 111 Schematic Diagram 1 Room Type Indoor Unit ...
Страница 113: ... 113 3 Art Cool Type Indoor Unit ...
Страница 114: ... 114 4 Convertible Type Indoor Unit RY 4WAY RY OUTFAN ...
Страница 120: ... 120 354212 249951 268714 266012 352114 263230 352118 330870 158591 3 Cassette Type Indoor Unit AMNN126EA0 AMNN186TEA0 ...
Страница 121: ... 121 346810 130411 359011 152312 135802 135312 2 W0CZZ 137211 267110 352150 352150 130911 140570 268712 146811 ...
Страница 132: ...P No 3828A20097N August 2003 Printed in Korea ...