Certifications
The Leybold refrigeration units listed below comply as
complete systems with the requirements of Underwriters
Laboratories (UL) as “Recognized Component“ (UR) and
the cUR certification awarded by Underwriters Laborato-
ries for the Canadian Standards Association.
The overall system comprises the
COOLPAK 6000-1
com-
pressor unit with the
CACP 6000
Adsorber and one or
more “
RGS
,
RGD
, or
COOLPOWER
“ cold heads, the type
“FL” flexlines and the accessories for single- and multi-
ple-head operation (type “GD” gas distributor, type “MC”
electrical distribution unit, etc.).
These Leybold refrigerator units are registered under the
recognition mark UR/cUR reference No. SA 8676.
Labelling for the system as a whole is to be found only
on the data plate for the compressor unit.
Warn and operation references
to Certification
Caution
If helium is added in the field or unit is
recharged the filling pressure should not
exceed 16
-1
bar (232
-14.5
psig). (Unit and
ambient temperature 20
°
C) The admissible
filling pressure dependent on the unit
design and operational conditions is defi-
ned in the Operating Instructions in Section
“1.3 Technical specifications“.
The system is to be used with up to 4 Leybold cold
heads type “
RGS
,
RGD
, or
COOLPOWER
“ using Leybold
flexible pressure lines type “
FL
“. For operation of more
than 1 cold head use Leybold electrical manifold “
MC
“
and suitable Leybold gas manifolds.
When the charcoal adsorber is replaced replace it with
the new Leybold adsorber type “
CACP 6000
“.
C
®
US