Table III - Thumbwheel Switch Settings

 

 
 

PACK NUMBER 

THUMBWHEEL SWITCH NUMBER 

 
 1 

 2 

 3 

 4 

 5 

 6 

 7 

 8 

 9 

 10 

 11 

10 

 12 

11 

 13 

12 

 14 

13 

 15 

14 

 16 

15 

 

Step 12 - Set Non-Dim switches

 

Note: if control module is not a Topaz Universal type, skip to the next step (Step 13). 
 

 Switch Non-Dim switches to select which dimmers are to operate in the Non-Dim mode.  The Non-Dim mode switches are located on the left-hand side of the top 

printed-circuit board on the Universal Control Module.  See Figure 9, page 7. In the off (left) position, the channel will function as a dimmer.  In the on (right) position, 
the dimmer will function as a non-dim (fully off or fully on).  Only the first twelve switches are used. 

CAUTION: Do not operate these switches while the pack is energized.

 

 

 

Step 13 - Apply power and check

 

 

Apply power to the pack.  Power indicator LED should be lit on the control module.  If the LED is not lit or is flashing, at least one control fuse is blown or one power 

leg has no voltage present.  Check the control fuses on the rear of the control module.  Check the feeder wiring with a meter, correct the problem and restore power to 
the pack.  See Figure 8. 

 

CAUTION: High Voltage - all measurements with a meter and other operations within the pack must be with the pack de-energized or by a 
qualified

 

electrical installer exercising extreme care.

 

 
 
 
 
 

 

 

 

 

 

 

 

Model 
No.

 

Max 
Load

 

 
Voltage 

Circuit 
Breaker 

166-361 
166-362 
166-364 

1.8kW 
2.4kW 
2.5kW 

120 
120 
220/240* 

15A 
20A 
15A 

  

  *(foreign electrical services only)

 

 

 

 

 

 

 

 

 

 

Step 14 - Install dimmers 

 

Unpack all dimmers. 

 

Slide a dimmer module into each dimmer slot beginning with the bottom dimmer slots first and building upward.  Push the dimmers in until they are seated firmly. 

 

 

 

 

 

Page 8

Содержание Topaz 12

Страница 1: ... GUIDE Part LIT 29499 1A Contractor Please read these instructions before starting installation After installation please forward this guide to the user for operation and maintenance instruction Copyright March 2002 Leviton Manufacturing Co Inc ...

Страница 2: ...k s 4 Connect power feeders 4 Connect load conductors 5 Low voltage application notes 5 Connect control conductors 6 Seal unused openings 6 Install control module s 7 Set thumbwheel switch es 7 Set Non dim switches 8 Apply power and check 8 Install dimmers 8 Install filler modules 9 Test loads 9 Close door 9 Maintenance and Specifications 10 Warranty 11 ...

Страница 3: ...rance in front for proper cooling and access Packs should be located in a clean dust free environment within proper operating temperature range See Specifications Table IV pg 10 One pack per location Note If you have a multiple pack or semi recessed installation skip ahead to the appropriate section for instructions Locate stud or a secure framing member in wall where pack is to be mounted Using t...

Страница 4: ...er nut and nuts not supplied Bush control wire knockout with T S chase nipple or equivalent not supplied Mount the pack assembly to the mounting channels using bolts and lockwashers Semi Recessed Packs Locate semi recessed mounting kit Model Number 600 906 shipped separately Mount the two mounting brackets to the sides of the pack with the 10 24 screws and lockwashers supplied Refer to Figure 2 Mo...

Страница 5: ...bottom or side conduit knockouts of the first pack Bottom or side access is preferable Figure 3 Conduit Entry Areas Bottom Conduit Knockouts Top Conduit Knockouts Step 4 Convert Bussing To Single Phase Packs are shipped ready to accept three phase 4 wire feeders If feeder is single phase 3 wire convert bussing as follows Otherwise skip to the next Step 5 Loosen the four bolts securing the feeder l...

Страница 6: ...phase neutral and ground lugs and tighten according to Table I See Figure 5 for lug locations If pack has been converted to single phase only lugs A C will be terminated N C B A NEUTRAL LUG PHASE LUGS GROUND LUG Figure 5 Power Lug Location Table I Line Terminal Torque Ratings 14 AWG 10 AWG 35 in lbs 2 6 mm2 Line and Neutral Lugs 8 AWG 40 in lbs rated for copper wire only 10 mm2 and for 90 C ampaci...

Страница 7: ...the current flowing in the transformer primary 120V side for all transformers connected to the dimmer module When calculating VA load keep in mind that transformer losses add many VA to the published VA load rating of the transformer When current cannot be measured derate the kW rating of the dimmer module by 25 and add up the kW ratings of the lamps involved Caution Operation of a dimmed transfor...

Страница 8: ... 7 For ease of assembly remove and discard TB2 Figure 7 TB3 CONTROL CONSOLE DLR INTERFACE OR PREVIOUS PACK ANALOG 0 10V For analog 0 10V applications a Universal Control Module must be used Locate the terminal blocks inside the Pack labeled 0 to 10VDC Dimmer Control Inputs Connect the incoming control wires to terminals 1 12 Connect to at least one common terminal per group of 12 inputs Step 9 Sea...

Страница 9: ...t in until it is fully seated Module No Control Module Type 120V 240V Foreign Electric Service Only TOPAZ 12 Remote LEC2102 LEC2105 TOPAZ 12 Universal 600 902 600 904 3 GANG DIP SWITCH S1 JUMPER JP5 CONTROL FUSES F1 3 RACK NO THUMBWHEEL SWITCH POWER INDICATOR TEST SWITCH Figure 8 Remote Control Module NON DIM SWITCHES Figure 9 Universal Control Module STATUS OTHER SWITCH AMX DMX SWITCH Step 11 Set...

Страница 10: ... is energized Step 13 Apply power and check Apply power to the pack Power indicator LED should be lit on the control module If the LED is not lit or is flashing at least one control fuse is blown or one power leg has no voltage present Check the control fuses on the rear of the control module Check the feeder wiring with a meter correct the problem and restore power to the pack See Figure 8 CAUTIO...

Страница 11: ...ol module to the TEST position See Figure 8 page 7 This will turn on the fan Switch on the circuit breaker of each dimmer one at a time by moving the breaker handle to the left Verify that the load is on and the dimmer is operating When testing is completed switch the test switch on each control module to the NORMAL position This will turn off the fan and all dimmers Verify that all circuit breake...

Страница 12: ...1 1 2 T S 1 concentric 1 2 3 4 Maximum Fan Noise Rating NC33 Maximum Ambient Operating Temperature 40 C 104 F Maximum Operating Humidity 90 without condensation Maximum Feeder Size 125 Amp Nominal Input 120 V Circuits 240V Circuits FOREIGN ELECTRICAL SERVICE ONLY 120 208V 3Ø 4W 50 60 Hz or 120 240V 1Ø 3W 50 60 Hz 240 415V 3Ø 4W 50 60Hz or 240 480V 1Ø 3W 50 60Hz Pack Enclosure NEMA Type 1 for indoo...

Страница 13: ...service during the warranty period Leviton NSI will repair at its option defective materials provided you have identified yourself as the original owner of the product to Leviton NSI or any authorized Leviton NSI dealer Transportation charges to and from an authorized dealer or the Leviton NSI factory for repair shall be the responsibility of the owner All products returned to Leviton NSI must hav...

Отзывы: