FEATURES
• Meets the requirements of Outdoor/Indoor installations conforming to IP 54 and NEMA 3R with
standard NEMA plugs and connectors.
• Meets the requirements of Outdoor/Indoor installations, conforming to IP 66, UL Standard
50, and NEMA Environmental Ratings of 4X,12K,
only
when used in conjunction with Leviton
WETGUARD
TM
plugs.
• For use with 20A - 30A NEMA locking plugs.
• Provides ON-OFF switched control for a connected load.
• This enclosure provides lockout capability in compliance with OSHA Lockout/Tagout
Regulation 29 CFR Part 1910.147 (in the OFF position) with an acceptable padlock/shackle,
thereby assuring the connected equipment cannot be energized.
• Auxiliary contact open prior to the line contacts for pilot duty switching.
NOTE:
This enclosure must not be used as a junction box for feed-through connections.
INSTALLATION INSTRUCTIONS
WARNING:
FOR INSTALLATION ONLY BY A qUALIFIED ELECTRICIAN IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE (NEC) OR THE CANADIAN ELECTRICAL CODE
(CEC), LOCAL CODES, AND THE INSTALLATION INSTRUCTIONS.
WARNING:
RISK OF ELECTRICAL SHOCK. DISCONNECT ALL POWER SUPPLIES TO
ENCLOSURE BEFORE EXPOSING INTERIOR. MORE THAN ONE SUPPLY DISCONNECT
MAY BE REqUIRED TO DE-ENERGIzE THIS EqUIPMENT BEFORE SERVICING.
WARNING:
RECEPTACLE MUST BE INSTALLED BEFORE CONNECTION TO A POWER
SUPPLY. 30A MAXIMUM RECEPTACLE RATING. REFER TO RATINGS TABLES AND WIRING
DIAGRAMS.
WARNING:
SEPARATE OVERCURRENT PROTECTION MUST BE PROVIDED IN
ACCORDANCE WITH THE NEC ARTICLE 220 OR CEC, SECTION B AS APPROPRIATE.
OVERCURRENT PROTECTION MUST NOT EXCEED THE AMPERE RATING OF THE
RECEPTACLE PER NEC SECTION 430-42(C) OR CEC PART 1, RULE 28-602 (3)(C)(I).
OTHER CAUTIONS AND NOTES:
1.
USE THIS DEVICE ONLY WITH COPPER OR COPPER CLAD WIRE. WITH ALUMINUM
WIRE USE ONLY DEVICES MARKED CO/ALR OR CU/AL.
2.
CHECK TO SEE THAT RATING MARKED ON DEVICE IS CORRECT FOR THE INTENDED
INSTALLATION.
3.
THE LOCKOUT FEATURE DOES NOT INTERRUPT THE POWER SUPPLIED TO THE
SWITCH.
4.
DEVICE IS SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE
THAN 600 VAC MAXIMUM.
5.
COVER CANNOT BE REMOVED WHEN SWITCH HANDLE IS IN THE “ON” POSITION.
6.
THESE ENCLOSURES MUST ALWAYS BE MOUNTED VERTICALLY WITH RECEPTACLE
END DOWN.