4.  CONNECTING MODEL 75A00-1 ACCESS CONTROL CARD READERS 

 

The 75A00-1 requires 4 wires for operation (2 for power and 2 for communications).  The maximum distance 
between the 75A00-1 and the LEVITON 83A00 Power Hub is based on two factors: 1) the current draw of the 
connected door lock device, and 2) the wire gauge/type used.  To maintain proper operation of the 75A00-1 and 
the connected door lock device, do not exceed the "Maximum Cable Length" based on the Total Current Draw 
and the Wire Gauge/Type per the table below (Table 1). 
 

 

75A00-1 Only (no Door Lock connected): 150mA maximum 

 

75A00-1 and 79A00-1 Electric Door Strike (450mA): 600mA 

maximum 

W ire 

Gauge

 

W ire 

Type 

Number 

of positive 

conductors 

Number 

of ground 

conductors 

M aximum 

Cable 

Length (feet) 

W ire 

Gauge

 

W ire 

Type 

Number 

of positive 

conductors 

Number 

of ground 

conductors 

M aximum 

Cable 

Length (feet) 

24 

solid 

233  

24 

solid 

58 

24 

solid 

466  

24 

solid 

117 

24 

solid 

699  

24 

solid 

175 

22 

solid 

413  

22 

solid 

103 

22 

solid 

826  

22 

solid 

207 

22 

stranded 

381  

22 

stranded 

95 

18 

solid 

1000  

18 

solid 

261 

18 

stranded 

963  

18 

stranded 

241 

16 

solid 

1000  

16 

solid 

415 

16 

stranded 

1000  

16 

stranded 

383 

 

75A00-1 and D oor Lock (800mA): 950mA maximum 

 

75A00-1 and Door Lock (1A): 1.15A maximum 

W ire 

Gauge

 

W ire 

Type 

Number 

of positive 

conductors 

Number 

of ground 

conductors 

M aximum 

Cable 

Length (feet) 

W ire 

Gauge

 

W ire 

Type 

Number 

of positive 

conductors 

Number 

of ground 

conductors 

M aximum 

Cable 

Length (feet) 

24 

solid 

37  

24 

solid 

30 

24 

solid 

74  

24 

solid 

61 

24 

solid 

110  

24 

solid 

91 

22 

solid 

65  

22 

solid 

54 

22 

solid 

130  

22 

solid 

108 

22 

stranded 

60  

22 

stranded 

50 

18 

solid 

16 5 

18 

solid 

136 

18 

stranded 

152  

18 

stranded 

126 

16 

solid 

262  

16 

solid 

217 

16 

stranded 

242  

16 

stranded 

200 

 

 

Table 1 

 

 

 
Note:

    If  cable  with  multiple  conductors  is  used  (such  as  Cat-5  cable),  it  is  possible  to  connect  multiple 

conductors together for power (i.e. the wires between Red and Black of the Access Control Reader and 12V and 
GND of the Power Hub) to achieve greater distance.   
 

 

WEB VERSION

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание 83A00-1

Страница 1: ...Power Hub Cat No 83A00 1 Installation Manual WEB VERSION www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Страница 2: ...ind into this product through openings as they may touch dangerous voltages Never install communications wiring or components during a lightning storm use in wet locations Never touch uninsulated wire...

Страница 3: ...osures 83A00 2 It is supplied with a sealed Power Pack which provides power to the LEVITON Power Hub Features 1 Connections for any 12VDC devices up to 5 Amps total 2 Connections for the following LEV...

Страница 4: ...OMNITOUCH TOUCHSCREENS RED WIRE TO BLACK WIRE TO YUASA NP7 12 OR EQUIVALENT 12V 7AH BATTERY 1 GROUNDING Each Power Hub MUST be grounded to the controller The LEVITON controller and LEVITON Power Hub...

Страница 5: ...municate on a different communications bus Connecting Devices of the Same Communications Type For example if all connected devices that communicate with the LEVITON controller consist of 75A00 1 Acces...

Страница 6: ...Switch SW1 must be in the DISCONNECT position See Figure 4 DEVICE 1 DEVICE 4 75A00 1 Access Control Readers must be connected on the first row DEVICE 1 DEVICE 4 DEVICE 5 DEVICE 8 Consoles and or OmniT...

Страница 7: ...lid 2 2 207 22 stranded 1 1 381 22 stranded 1 1 95 18 solid 1 1 1000 18 solid 1 1 261 18 stranded 1 1 963 18 stranded 1 1 241 16 solid 1 1 1000 16 solid 1 1 415 16 stranded 1 1 1000 16 stranded 1 1 38...

Страница 8: ...ure 5 Connect the supplied 4 conductor reversed modular cable gray cable between one of the modular connectors J301 or J302 on the Power Hub and a serial port J2 J5 on the LEVITON controller See Figur...

Страница 9: ...mina Pro controller if additional power is needed to control the required Access Control Readers and connected locks or if there are long distances between Access Control Readers and the LEVITON contr...

Страница 10: ...L WHEN A SERIAL INTERFACE IS CONFIGURED FOR ACCESS CONTROL THE CORRESPONDING INTERFACE JUMPER JP1 JP5 MUST BE IN THE 485 POSITION CONTROLLER MODEL 83A00 12VDC POWER HUB Figure 7 Gray reversed Cable Bl...

Страница 11: ...e of the 24 gauge conductor in the Cat 5 cable for power 1 for positive and 1 for ground the maximum distance between the controller and the touchscreen is 113 feet 2 The distance between the Power Hu...

Страница 12: ...REENS AND OR Figure 8 Connect the terminals labeled A and B under the section marked CONTROLLER on the Power Hub to the terminals labeled A and B under the section marked CONSOLE on the LEVITON contro...

Страница 13: ...NNECTIONS The supplied Power Pack is used to power the LEVITON Power Hub An AC power outlet should be located within 5 feet One or two sealed rechargeable batteries not included can be used to backup...

Страница 14: ...nstalled and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation...

Страница 15: ...to which the receiver is connected Consult the dealer or an experienced radio TV technician for help LEVITON LIMITED WARRANTY Leviton warrants to the original consumer purchaser and not for the benefi...

Отзывы: