SW6000 SEISMIC VIBRATION SWITCH

Installation Manual

OVERVIEW

The SW6000 Seismic Vibration Switch offers 

basic protection against gross changes in 

structural seismic acceleration.  

This electronic switch is a versatile exces

-

sive vibration protection instrument. In its 

standard configuration, the SW6000 is an 

economical single set point vibration switch 

with standard features and packaged in 

industrial grade housing with available haz

-

ardous area certifications. Fully configured, 

the SW6000 provides for local machine 

control with optional LCD readout and real 

time remote operator interface via a 4-20 

mA output.

SUPPLEMENTARY INFORMATION

Refer to Metrix Datasheet #1009462 and 

Metrix Installation Manual for Hazardous 

Areas #100867 available at www.metrixvi

-

bration.com. 

Содержание SW6000

Страница 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Страница 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Страница 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Страница 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Страница 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Страница 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Страница 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Страница 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Страница 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Страница 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Страница 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Страница 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...