Installation & Operation Guide
Installation & Operation Guide
Page 6
LOAD WIRING
The 2408 CD/CR can provide eight tungsten or resistive branch
lighting circuits of 120V AC at 20 amps each. If the lighting loads
are expected to operate continuously at full power for three hours
or more, then the load must not exceed 16 amps in accordance with
electrical codes.
The load wiring should be at least #12 AWG in size and must be
copper wire rated for at least 75 C such as THWN .The load wiring
may exit through either of the 1/2”- 3/4” knockouts located in the
load wiring compartment or may exit through the top of the unit.
2408 CD
The live wire (black) of each load connects to the copper terminal
located below each filter coil. The neutral wires (white) for all loads
connect to the neutral bar located near the circuit breakers. If the
loads require individual ground wires, these will connect to the
ground bar located in the load-wiring compartment.
2408 CR
The live wire (black) of each load connects directly to the 1/4”
quick-connect tabs of the solid state power cubes using the yellow
crimp-on connectors provided. The channel number corresponding
to the power cube tab is indicated on the cube. The neutral wires
(white) for all loads connect to the neutral bar located near the
circuit breakers. If the loads require individual ground wires,
these will connect to the ground bar located in the load-wiring
compartment.
INSTALLATION