DMX-512 multiple control wiring

DMX-512 is the preferred type of control wiring because of the high 

update rate and the resistance to interference. It is highly recommended 

in locations subject to electrical noise. DMX-512 only requires 3 wires 

transmit lighting levels to as many as 512 dimmer channels. DMX-512 

should not be used simultaneously with Microplex. Most of the Leviton 

lighting control consoles can use this interface.

Connect the three DMX-512 control wires to the appropriate terminals 

provided on the power supply card. Duplicate terminals are provided 

to carry the control connections to more dimmer packs if necessary. Be 

sure to set the Channel Address on the dipswitches of the dimmer firing 

cards as required. If a+ 15 VDC power source is required for the control 

console, connect an additional wire to the + 15 VDC terminal on the 

power supply board. This wire and the common wire must be at least 

18 gauge. This power supply can deliver 750 MA maximum and can be 

connected in parallel to other 2408 CD/CR packs. 

If a +15 VDC power source is required for the control console, connect 

an additional wire to the + 15 VDC terminal on the power supply board. 

This wire and the common wire must be at least 18 gauge. This power 

supply can deliver 750 MA maximum and can be connected in parallel to 

other 2408 CD/CR packs.

Microplex multiplex control wiring

Microplex is the control protocol used on all Leviton lighting console. This 

system uses a shielded wire to transmit up to 128 channels of dimmer 

control. Microplex should not be used simultaneously with DMX-512. For 

short distances (50 feet) a standard microphone cable is used to carry 

both the control signal and the DC power source for Leviton control 

consoles. Longer distances may be accommodated with 18 gauge or 

better cable to reduce voltage losses of the power supply.

Connect the Microplex control wires to the appropriate terminals on 

the power supply card. If an XLR type connector is used to connect the 

control console, connect pin 1 to common, pin 2 to + 15 VDC, and pin 

3 to MICROPLEX. A duplicate set of connections is provided to carry the 

control signal to more dimmer packs. Be sure to set the Channel Address 

dip switch as required. 

SWITCH SETTINGS

When using any of the multiplex control systems the dip switches on 

the 2408 CD/CR must be set to assign the desired dimmer channels. 

The switches control the dimmer channels in groups of four. The dip 

switch on the left dimmer firing card controls circuit channels 1-4 

while the dip switch on the right card controls circuit channels 5-8 of 

the pack. Both switches may be set to the same settings if only four 

control channels are desired. See the following chart for settings.

DIPSWITCH CHANNEL ASSIGNMENTS

CONTROL

1234567 CONTROL 1234567

CONTROL

1234567

1-4

0000000

5-8

1000000

9-12

0100000

13-16

1100000

17-20

0010000

1-24

1010000

25-28

0110000

29-32

1110000

33-36

0001000

37-40

1001000

41-44

0101000

45-48

1101000

49-52

0011000

53-56

1011000

57-60

0111000

61-64

1111000

65-68

0000100

69-72

1000100

73-76

0100100

77-80

1100100

81-84

0010100

85-88

1010100

89-92

0110100

93-96

1110100

97-100

0001100

101-104

1001100

105-108

0101100

109-112

1101100

113-116

0011100

117-120

1011100

121-124

0111100

125-128

1111100

129-132

0000010

133-136

1000010

137-140

0100010

141-144

1100010

145-148

0010010

149-152

1010010

153-156

0110010

157-160

1110010

161-164

0001010

165-168

1001010

169-172

0101010

173-176

1101010

177-180

0011010

181-184

1011010

185-188

0111010

189-192

1111010

193-196

0000110

197-200

1000110

201-204

0100110

205-208

1100110

209-212

0010110

213-216

1010110

217-220

0110110

221-224

1110110

225-228

0001110

229-232

1001110

233-236

0101110

237-240

1101110

241-244

0011110

245-248

1011110

249-252

0111110

253-256

1111110

257-260

0000001

261-264

1000001

SWITCH SETTIN

GS

Содержание 2408CD

Страница 1: ...201 North Service Road Melivlle N Y 11747 Telephone 1 800 323 8920 FAX 1 800 832 9538 Visit Leviton s Web site at http www leviton com 2016 Leviton Manufacturing Co Inc All Rights Reserved Specifications and Price Subject to Change at any time without notice DI 400 N2408 00D 20 OFF O O OFF 20 O OFF 20 20 OFF O 20 OFF O O OFF 20 20 OFF O 20 O OFF 8 6 7 5 4 CIRCUIT BREAKERS ON 2 3 1 OFF COMMERCIAL D...

Страница 2: ......

Страница 3: ...____________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________...

Страница 4: ...__________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _________________________...

Страница 5: ...ls or other obstructions Adequate side and top clearances from adjacent walls and equipment are necessary If several units are to be installed in a small enclosed room adequate ventilation must be provided to prevent the room temperature from exceeding 100 degrees Fahrenheit Clear working space and access to the 2408 CD CR must be provided in accordance with electrical codes INSTALLATION Minimum d...

Страница 6: ...ance Department 165 Hymus Blvd Pointe Claire Quebec Canada H9R 1E9 or by telephone at 1 800 405 5320 Figure 2 INPUT WIRING LOADS MAY EXIT TOP 20 AMP CIRCUIT BRKRS 20 AMP CIRCUIT BRKRS GND NEUTRAL BUS Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under no...

Страница 7: ...the unit 2408 CD The live wire black of each load connects to the copper terminal located below each filter coil The neutral wires white for all loads connect to the neutral bar located near the circuit breakers If the loads require individual ground wires these will connect to the ground bar located in the load wiring compartment 2408 CR The live wire black of each load connects directly to the 1...

Страница 8: ...levels at the programmed fade rate Release button when correct lighting levels are attained To lower lighting levels with a 400CP remote Press and hold the decrease button of the zone desired If the unit is in the power down state power will come on in 1 4 second The 400CP will then take control of all dimmer channels assigned to the selected zone and decrease lighting levels at the programmed fad...

Страница 9: ...mer channels of the 2408 CD CR may be operated by a 0 10 VDC control voltage This type of control will provide 0 intensity at 0 volts and 100 intensity at 10 volts Any or all of the dimmer channels may be operated in this manner simultaneously with either of the multiplex control inputs Each dimmer will respond to the greater of any control inputs Connect each of the plus control wires to the desi...

Страница 10: ...ith 18 gauge or better cable to reduce voltage losses of the power supply Connect the Microplex control wires to the appropriate terminals on the power supply card If an XLR type connector is used to connect the control console connect pin 1 to common pin 2 to 15 VDC and pin 3 to MICROPLEX A duplicate set of connections is provided to carry the control signal to more dimmer packs Be sure to set th...

Страница 11: ...SPCL on the It is also a good idea to make sure the jumper is installed across both jumper pins marked SOFTSTART CD s only For Stage Lighting Systems Make sure the jumper block on each control card is NOT across both jumper pins marked SPCL You must also remove the SOFTSTART jumper on each control card so the lights will not appear sluggish in response NON DIM CHANNELS Any of the channels of the 2...

Страница 12: ...f 50 instead In theatrical stage lighting systems this feature may not be desirable since the dimming system is turned off frequently SOFTSTART The 2408 CD comes from the factory configured in the SOFTSTART operating mode This mode of operation forces at least a 1 10th second delay between the output being full off to the output being full on to allow a more gradual warming of the lamp filaments T...

Отзывы: