Parameter- reset respc. copy Parameter.
Notice!
A valid parameter set operation must be acknowledged with 'PS0'. Should an
error occur, the command should be repeated. Repeated error acknowledge-
ments indicate an error in the parameter set. If in doubt, contact your Leuze
sales or service office (see back page for addresses).
Command
’PC’
Description
Copies the given source parameter set into the given target parameter set
Parameter
'0'
current parameter set.
'1'
customer-specific parameter set.
'2'
parameter set with factory default settings.
Examples:
'PC20'
: Parameter Reset (to factory settings).
'PC01'
: The current parameter set is copied in the customer-specific
parameter set (backup).
'PC10'
: Reset to customer-specific settings!
Attention!
With this command, the parameter sets of any connected bar
code reader will be influenced in the same way.
Acknowledge-
ment
All possible acknowledgements are listed below.
Acknowledgement
Description
'PS0'
valid parameter set.
'PS1'
other invalid message.
'PS2'
invalid message length.
'PS3'
invalid type of BCC check sum.
'PS4'
invalid BCC check sum.
'PS5'
invalid data length.
'PS6'
invalid message parameters.
'PS7'
invalid start address in parameter set.
'PS8'
invalid CRC check sum of parameter set.
'PS9'
invalid type of parameter set.