Troubleshooting
26
SOLID-2SF-M
Leuze electronic
Review status, , Mittwoch, 8. April 2015
DEUTSCH
E
NGLISH
FRAN
ÇAIS
ITALIA
N
O
ESPAÑOL
N
EDERLANDS
Table 7.2:
Receiver diagnostics
7.3
AutoReset
After an error or a fault has been detected and displayed, an automatic restart occurs within
• about 2 seconds for the Transmitter
• about 20 seconds for the Receiver
for the device in question. If the error or fault is then no longer present, the machine or
system can be started again.
E 06
Short circuit of an SSD against GND or cross
connection between two SSDs or between SSD and
Dyn SSD
Eliminate cross connection
E 07
Short circuit of an SSD a24V DC or cross
connection between two SSDs or between SSD and
Dyn SSD
Eliminate cross connection
E 14
Power supply undervoltage
Check/replace power supply or load
E 18
Test time-limit exceeded
Test time > 150 ms; check external test
E 22
Power supply cable overvoltage
Check power supply/load
Code Cause/meaning
Measure to eliminate error