Function of the IO switching input (pin 2)
The switching input is configured via index accesses only (see Table 5.6).
Two functions are available which can be activated via the switching input.
Activation
A high signal at the switching input activates the sensor illumination; a low signal deactivates
the sensor illumination.
Deactivation
A high signal at the switching input deactivates the sensor illumination; a low signal activates
the sensor illumination.
NOTE
Output behavior with deactivated sensor illumination
With the sensor illumination deactivated, the sensor does not deliver any measurement
values.
In this case, the output behavior of the switching output (pin 2, pin 4) with the trace moni-
toring or contrast monitoring function can be controlled via UART index 76
d
(CANopen
index 2005
h
)
Qproperty
.
This setting has no effect on the output of process data.
NOTE
Deactivation of the switching input
The switching input IO can also be deactivated.