Diagnostics and troubleshooting
Leuze electronic
MSI-MD-FBX
38
Error
Cause/description
Remedies and measures
Behavior of the
muting controller
U35
Sequence error if muting sen-
sor 3 and muting sensor 4 are
activated and muting sensor 3
should be free
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U41
Concurrency expectation of
the muting signals not met:
second signal outside toler-
ance of 4 s
Check the arrangement of the mut-
ing sensors or the programming of
the machine interface if required.
Automatic reset
U43
Muting end before protective
field release
Select a valid muting condition.
Automatic reset.
U44
Sequence error if muting sen-
sor 1 and muting sensor 2 are
activated and muting sensor 2
should be free
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U45
Sequence error if muting sen-
sors 1 to 3 are activated and
muting sensor 3 should be free
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U46
Sequence error if all muting
sensors are activated and mut-
ing sensor 4 should be free
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U47
Sequence error between mut-
ing sensor 2 and muting sen-
sor 1
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U48
Sequence error between mut-
ing sensor 3 and muting sen-
sor 2
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U49
Sequence error between mut-
ing sensor 4 and muting sen-
sor 3
Check the arrangement and align-
ment of the muting sensors
Automatic reset
U50
Muting restart without valid
muting configuration of the
muting sensors
Check the mounting of the muting
sensors and the activation of the
muting signals.
Automatic reset
U51
Only one muting signal active
in case of protective field viola-
tion, the second muting signal
is missing
Check the mounting of the muting
sensors and the activation of the
muting signals.
Automatic reset
U52
Oscillating muting sensor de-
tected
Check the wiring or whether the
muting sensor is defective. Ex-
change the muting sensor if nec-
essary.
Automatic reset.
U55
Time limit for override ex-
ceeded
Check the further processing of
the OSSD signals and the design
of the muting system.
Automatic reset
U56
Acknowledgment unit was ac-
tuated with interrupted protec-
tive field and without activated
muting sensor
Check the arrangement and con-
nections of the muting sensors and
carry out muting restart again if re-
quired.
Automatic reset
U58
Muting timeout elapsed
Actuate the acknowledgment unit
Automatic reset
U59
A muting sensor has switched
on and off again multiple times
without muting having been
triggered
Check the arrangement and align-
ment of the muting sensors.
Automatic reset