Starting up the device - Configuration
Leuze electronic
MSI-MD-FBX
32
DIP
switch
Function
ON
OFF
7/8
Muting timeout
OFF/OFF: 20 seconds
OFF/ON: 2 minutes
ON/OFF: 10 minutes
ON/ON: 100 hours
Setting the operating mode
The following table lists the permissible operating modes that can be set via the DIP switch blocks.
After the device is started, the 7-segment display of the muting controller shows the set operating mode.
NOTICE
This muting controller can only be operated in operating mode 7.
NOTICE
Error in event of impermissible setting of DIP switches!
If a DIP switch configuration is set that does not correspond to that of a permissible operating
mode, an operating mode error is triggered and the OSSDs switch off.
Ä
Only set one of the DIP-switch configurations listed in the operating mode table.
NOTICE
Restart interlock for access guarding!
For access guarding, a restart interlock is required.
Ä
If the
automatic restart interlock
is configured in the muting controller, you must carry out the
restart interlock, e. g. via the machine interface.
Tab. 8.2:
Operating modes
DIP
switch
1
2
3
4
5
6
Function
Number of
muting sen-
sors
Muting mode
EDM
Restart
Muting-en-
able
Muting-time-
out exten-
sion
Operating
mode
7
2-sensor
Timing con-
trolled
Without
Manual
With
Without