Device description
22
MA 248
i
Leuze electronic
The MA 248
i
supports:
• PROFINET-IO device functionality based on the PROFINET profile for identification
systems
• Modular structure of the IO data
• PROFINET-IO RT (
R
eal
T
ime) communication
• Standard Fast EtherNet (100 Mbit/s) connections (M12 technology)
• Integrated EtherNet switch / 2 EtherNet ports
• PROFINET-IO Conformance Class B (CC-B)
• I&M support: I&M 0-4
• Diagnostics / alarms
For further details, see chapter 12!
Identification & Maintenance Functions
The MA 248
i
supports the base record I&M0:
Table 4.1:
Base record I&M0
The MA 248
i
supports further protocols and services for communication:
• TCP/IP (firmware upload via web server)
• DCP
• ARP
• PING
Further information on commissioning can be found in chapter 12.
Contents
Index
Data type
Description
Value
Header
0
10 bytes
Manufacturer specific
MANUFACTURER_ID
10
UNSIGNED16
Leuze PNO manufacturer ID
338
ORDER_ID
12
ASCII string 20 bytes
Leuze order no.
Device-
dependent
SERIAL_NUMBER
32
ASCII string 16 bytes
Unique device serial number
Device-
dependent
HARDWARE_REVISION
48
UNSIGNED16
Hardware revision number, e.g.,
"0…65535"
Device-
dependent
SOFTWARE_REVISION
50
1xCHAR, 3xUNSIGNED8 Software version number, e.g., V130
corresponds to "V1.3.0"
Device-
dependent
REVISION_COUNTER
54
UNSIGNED16
Is incremented when updating individual
modules
This function is not supported
0
PROFILE_ID
56
UNSIGNED16
PROFINET application profile number
0xF600
(generic device)
PROFILE_SPECIFIC_TYPE
58
UNSIGNED16
Info about subchannels and submodules
Not relevant
0x01,0x01
IM_VERSION
60
2xUNSIGNED8
Implemented I&M version V 1.1
0x01,0x01
IM_SUPPORTED
62
Bit[16]
Optional I&M records available
0