Electrical connection
Leuze electronic
Technical description LES
49
TNT
35/7-2
4
V
6.3.3
Connection X3 - switching inputs/outputs (only LES 36/VC6 and LES 36HI/VC6)
Switching outputs of connection X3
Out1 to Out4 are each a logic combination of analysis results of the individual AWs. This
logic operation is defined in LRSsoft (see chapter 9.4 "Parameter settings/Parameters tab").
Up to 16 different logic combinations of the AW's and respective result mappings on Out1
to Out4 can be combined into inspection tasks.
Switching inputs of connection X3
The 3 switching inputs InSel1-3 are used to select the inspection task 0-7. In this context,
"000" stands for Inspection Task 0, "001" for Inspection Task 1, etc. The switching time
between 2 inspection tasks is < 100ms
Notice!
The Inspection Tasks 8-15 can be switched via PROFIBUS or Ethernet. The setting via
Ethernet overwrites the inspection task set via input InSel1-3.
X3 (8-pin socket, A-coded)
Pin
Name
Core color
Remark
1
Out4
WH
Output detection result 4
2
Out3
BN
Output detection result 3
3
GND
GN
Ground
4
Out2
YE
Output detection result 2
5
Out1
GY
Output detection result 1
6
InSel3
PK
Selection Inspection Task Bit 3
(MSB)
7
InSel2
BU
Selection Inspection Task Bit 2
8
InSel1
RD
Selection Inspection Task Bit 1
(LSB)
Table 6.5:
Pin assignment X3
Out4
InSel 1
Out3
GND
Out2
InSel 3
InSel 2
Out1
X3
7
8
M12 socket
(A-coded)