Integration of the LES 36/PB in the PROFIBUS
Leuze electronic
Technical description LES
115
TNT
35/7-2
4
V
11.3
General information about the GSD file
If the LRS is operated in a PROFIBUS network, configuration can be performed exclusively
via the LESsoft configuration software. The functionality of the inputs/outputs of the light
section sensor to the control is defined via modules. Using a user-specific configuration tool,
the respective required modules are integrated and configured according to the measure-
ment application during PLC programming.
During operation of the light section sensor on the PROFIBUS, the functionality of the inputs/
outputs is assigned default values. If these values are not changed by the user, the device
operates with the default setting set by Leuze electronic on delivery. Please refer to the
following module descriptions for the default settings of the device.
Notice!
At least one module from the GSD file must be activated in the configuration tool of the
control, usually
module M1, M2 or M3
.
Notice!
Some controls make available a so-called "universal module". This module must not be
activated for the LES 36/PB.
Attention!
The device makes available a PROFIBUS interface and an Ethernet interface. Both
interfaces can be operated in parallel.
Notice!
For test purposes, parameters can be changed on a LES 36/PB operated on PROFIBUS.
At this time, object detection is not possible on PROFIBUS.
Notice!
All input and output modules described in this documentation are described
from the
perspective of the control
:
Described inputs (I) are inputs in the control.
Described outputs (O) are outputs in the control.
Described parameters (P) are parameters of the GSD file in the control.
Notice!
The current version of the GSD file
LEUZE403.GSD
for the LES 36/PB can be found on the
Leuze website at
Download -> detect -> Measuring sensors
.