PARAMETER-SETTING MANUAL

VARMECA 10

Variable speed motors and geared motors

COMMISSIONING THE CDC-VMA CONSOLE

LEROY-SOMER

Ref. 3264 - 4.33/b -1.00

2.5 - The VARMECA 10 parameters

List and description of the parameters which can be accessed by the CDC-VMA console

Display

Description

Adjustment range in 

increments of 1

Factory setting

P01 F min

minimum operating frequency

6 to 30 Hz

12 Hz

P02 REF 0 V - 4 mA

calibration of the min. reference 
0 V or 4 mA

0 to 30 Hz

12 Hz

P03 F max

maximum operating frequency
(according to mini DIP K2 position)

32 to 220 Hz

50 or 80 Hz

P04 REF 10 V - 20 mA

calibration of the max. reference 

32 to 220 Hz

50 or 80 Hz

P05 ACCEL.

acceleration ramp
ramp value to pass from 0 to 50 Hz

0 to 20 s

3 s

P06 DECEL.

deceleration ramp
ramp value to pass from 50 to 0 Hz

0 to 20 s

3 s

P07 STOP MODE

stop mode

0 = freewheel stop
1 = stop according to ramp

0 or 1

1

P08 UN MOT
(1)

voltage applied to the motor from the base frequency
(percentage of mains voltage: base 400 V)

0 to 100 %

100 %

P09 FN MOT
(1)

motor base frequency

50 to 150 Hz

50 Hz

P10 U / F
(1)

selection of voltage/frequency ratio
0 = fixed U / F 
the P08 voltage will be applied at the P08 frequency point 
1 = dynamic U / F 
the voltage adapts automatically to the motor load 

0 or 1

0

from 0.25 to 1.1 kW

1

from 1.5 to 7.5 kW

P11 BOOST
(1)

value of voltage applied in low frequencies
(percentage of mains voltage)

0 to 40 %

adapted to the 

motor according to 

the power

P12 OVER BOOST
(1)

value of voltage during starting phase
(percentage of mains voltage)

0 to 100 %

adapted to the 

motor according to 

the power

P13 F PWM

switching frequency

0 = 4 kHz
1 = 6 kHz
2 = 8 kHz
3 = 11 kHz

0 to 3

3

from 0.25 to 2.2 kW

2

from 3 to 4kW

P14 CONFIG

terminal block configuration

0 = standard
1 = option 1 - 2 preset speeds and 2 operating 

directions

2 = option 2 - analogue reference and 3 preset 

speeds - 1 operating direction

3 = option 3 - correction of an external reference 

with the local button - 2 operating directions

4 = option 4 - 2 preset speeds proportional to the 

reference - 1 operating direction

0 to 4

0

P15 VP1-1

preset speed 1 in options 1 and 4

6 to 220 Hz

50 Hz

P16 VP2-1 VP1-2

preset speed 2 in options 1 and 4 or preset speed 1 in 
option 2

6 to 220 Hz

60 Hz

P17 VP2-2

preset speed 2 in option 2

6 to 220 Hz

40 Hz

P18 VP3-2

preset speed 3 in option 2

6 to 220 Hz

70 Hz

(1) : the voltage/frequency ratio is illustrated at the end of the table

en

Содержание VARMECA 10

Страница 1: ...This manual is to be given to the end user VARMECA 10 Variable speed motors and geared motors 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Parameter setting manual Ref 3264 4 33 b 1 00 en ...

Страница 2: ...ontrolled by an external safety system emergency stop fault detector The VARMECA 10 motor is fitted with safety devices which in the event of a fault control stopping and thus stop the motor The motor itself can become jammed for mechanical reasons Voltage fluctuations and in particular power cuts may also cause the motor to stop The removal of the causes of the shutdown can lead to restarting whi...

Страница 3: ...rage and correct handling must be observed The climatic conditions specified in the technical manual must be observed 4 Installation The installation and cooling of equipment must comply with the specifications in the manual supplied with the product VARMECA 10 motors must be protected against excessive stress In particular there must be no damage to parts and or modification of the clearance betw...

Страница 4: ... of the CDC VMA console 30 1 4 Wiring diagrams 31 2 COMMISSIONING THE CDC VMA CONSOLE 37 2 1 Installation 37 2 2 Presentation of the keypad 37 2 3 Read mode 38 2 4 Parameter setting mode 38 2 5 The VARMECA 10 parameters 39 3 COMMISSIONING THE PEGASE VMA 10 PC PARAMETER SETTING SOFTWARE 41 3 1 Connection 41 3 2 Installing the software 41 3 3 Use 42 3 4 The VARMECA 10 parameters 43 4 TROUBLESHOOTING...

Страница 5: ...ng the software onto a PC or 1 CD ROM 1 parameter setting manual MINIMUM PC CONFIGURATION Pentium 100 MHz 8 Mb of RAM WINDOWS 95 or 98 1 3 Weight and dimensions of the CDC VMA console See the following diagram 165 85 113 15 28 20 9 5 Weight 0 3 kg CDC VMA MEM P01 FMIN P02 REF 0V 4MA P03 F MAX P04 REF 10V 20MA P05 ACCEL P06 DECEL P07 STOP MODE P10 U F P11 BOOST P23 F MOT P24 I MOT FREQUENCE MIN HZ ...

Страница 6: ...6 5 Ramp selection logic input 1s 50 Hz terminals 5 and 6 not connected 3s 50 Hz terminals 5 and 6 connected 6 0 V common with terminal 4 7 Logic input run reverse stop 8 Logic input run forward stop 9 10 Relay output 250 V 1A Switched off or faulty On 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Fault relay 10V Local button or external potentiometer 0 10V speed image output 0V Ramp selection 0V Run reverse s...

Страница 7: ... common with terminal 6 5 Logic input S1 6 0 V common with terminal 4 7 Logic input run reverse stop 8 Logic input run forward stop 9 10 Relay output 250 V 1A Switched off or faulty On 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Fault relay 0 10V speed image output 0V Preset speed selection S1 0V Run reverse stop Run forward stop MAINS SUPPLY Associated parameter setting CDC VMA PEGASE VMA 10 Terminal block ...

Страница 8: ... V common with terminal 4 7 Logic input run forward stop 9 10 Relay output 250 V 1A Switched off or faulty On 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Fault relay 10V External potentiometer or external reference 0 10V speed image output 0V Preset speeds 0V Run stop Preset speeds S1 S2 MAINS SUPPLY Associated parameter setting CDC VMA PEGASE VMA 10 Terminal block configuration P14 2 OPTION 2 P16 VP1 2 Hz V...

Страница 9: ...input for enabling disabling the correction S1 open correction possible S1 closed no correction 6 0 V common with terminal 4 7 Logic input run reverse stop 8 Logic input run forward stop 9 10 Relay output 250 V 1A Switched off or faulty On 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Fault relay 0V 0V Enable disable local button 0V 10V Run reverse stop Run forward stop External reference 0 10V 4 20mA 1 2 3 4 ...

Страница 10: ...op 8 Logic input S3 9 10 Relay output 250 V 1A Switched off or faulty On 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Fault relay 10V External potentiometer or external reference Fixed or proportional preset speed selection 0V Preset speed selection 0V Run stop Stopping mode S1 S2 S3 MAINS SUPPLY Associated parameter setting CDC VMA PEGASE VMA 10 Terminal block configuration P14 4 OPTION 4 P15 VP1 Hz VP1 OPTI...

Страница 11: ...ference selection 6 0 V common with terminal 4 7 Logic input run reverse stop 8 Logic input run forward stop 9 10 Relay output 250 V 1A Switched off or faulty On 1 2 3 4 5 6 7 9 L1 L2 L3 PE 10 8 Fault relay 10V PI reference local button or external reference PI sensor feedback 0 10V 0V PI reference selection local button or external reference 0V Run reverse stop Run forward stop S1 MAINS SUPPLY As...

Страница 12: ...cket 20 pin socket 230 V power supply VARMECA 10 connector CDC VMA MEM P01 FMIN P02 REF 0V 4MA P03 F MAX P04 REF 10V 20MA P05 ACCEL P06 DECEL P07 STOP MODE P10 U F P11 BOOST P23 F MOT P24 I MOT FREQUENCE MIN HZ ETALONNAGE CONSIGNE MIN HZ FREQUENCE MAX HZ ETALONNAGE CONSIGNE MAX HZ HZ RAMPE ACCEL RAMPE DECEL S MODE D ARRET 0 ROUE LIBRE 1 RAMPE LOI U F 0 FIXE 1 DYNAMIQUE BOOST LECTURE FREQUENCE MOTE...

Страница 13: ...or scrolling in the opposite direction 2 4 Parameter setting mode To modify a setting use the or keys to select the parameter The key is used to make the parameter which is to be modified flash Modify the setting value with the or keys As soon as the value differs from the stored value the MEM message appears When the desired setting value has been reached it can be stored using the key The MEM in...

Страница 14: ...uency ratio 0 fixed U F the P08 voltage will be applied at the P08 frequency point 1 dynamic U F the voltage adapts automatically to the motor load 0 or 1 0 from 0 25 to 1 1 kW 1 from 1 5 to 7 5 kW P11 BOOST 1 value of voltage applied in low frequencies percentage of mains voltage 0 to 40 adapted to the motor according to the power P12 OVER BOOST 1 value of voltage during starting phase percentage...

Страница 15: ...to 220 Hz P24 I_MOT motor current in tenths of an ampere A 10 0 to 150 of In P25 FAULT last fault in memory fault code 0 no fault 1 motor overheating 2 overvoltage 3 overcurrent 4 locked rotor 5 DC bus undervoltage 6 EEPROM 7 serial link 8 power module fault 0 to 8 0 P26 STOP Fmin enabling of the STOP USING REFERENCE function 0 disabled 1 enabled when the reference is less than Fmin it forces the ...

Страница 16: ...et 3 disks or 1 CD ROM 1 parameter setting manual 3 1 2 Connection The RS 232 socket on the cable is connected to the RS232 socket on the PC The 20 pin socket on the cable connects to the connector on the VARMECA 10 rolled cable 3 2 Software installation Start up your PC Insert disk n 1 or the CD ROM Open the install file Follow the instructions given on the screen in particular those relating to ...

Страница 17: ...TWARE LEROY SOMER Ref 3264 4 33 b 1 00 3 3 Use Double click on the icon The first window appears 3 3 1 Detail of the 1st window 3 3 2 Detail of the 2nd window Choice of language Go to next window Exit the current window Power rating selected Go to next window VARMECA software version Programming software version Exit the current window ...

Страница 18: ...Hz 50 or 80 Hz F min minimum operating frequency 6 to 30 Hz 12 Hz ACCEL acceleration ramp value to pass from 0 to 50 Hz 0 to 20 s 3 s DECEL deceleration ramp value to pass from 50 to 0 Hz 0 to 20 s 3 s Un mot 1 voltage applied to the motor at base frequency percentage of mains voltage base 400 V 0 to 100 100 Fn mot 1 base frequency of motor 50 to 150 Hz 50 Hz BOOST 1 value of voltage applied in lo...

Страница 19: ...3 correction of an external reference using the local button option 4 2 preset speeds proportional to the reference standard option 1 option 2 option 3 option 4 standard VP1 option 1 4 preset speed 1 in configuration options 1 and 4 0 to 220 Hz 50 Hz VP2 option 1 4 VP1 option 2 preset speed 2 in configuration options 1 and 4 or preset speed 1 in configuration option 2 0 to 220 Hz 60 VP2 option 2 p...

Страница 20: ...increments of 1 Factory setting F mot motor frequency reading 0 to 220 Hz reading V bus voltage of the speed controller DC bus reading from 0 to 800 V Status speed controller status stop or run Fault speed controller fault indication POSSIBLE INDICATIONS no fault motor overheating overvoltage overcurrent locked rotor bus undervoltage EEPROM serial link module fault NO FAULT Vmains V bus 2 U motor ...

Страница 21: ... that the deceleration ramp is long enough for applications with high inertia check the set rating and the motor power internal product fault 4 LOCKED ROTOR Red LED illuminated check if the motor is overloaded or has stalled green LED flashing 5 BUS UNDERVOLTAGE Red LED flashing check the mains supply voltage 6 EEPROM Red LED illuminated make sure that the VARMECA 10 is not affected by interferenc...

Страница 22: ...duct be needed Settings made using the CDC VMA console Settings made using the PEGASE VMA 10 software Parameters Value set P01 F MIN P02 REF 0 V 4 mA P03 F MAX P04 REF 10 V 20 mA P05 ACCEL P06 DECEL P07 STOP MODE P08 Un MOT P09 Fn MOT P10 U F P11 BOOST P12 OVERBOOST P13 F PWM P14 CONFIG Parameters Value set P15 VP1 1 P16 VP2 1 VP1 2 P17 VP2 2 P18 VP3 2 P19 ROTATION P20 SELECT 3 P21 PI K PRO P22 PI...

Отзывы: