36
PARAMETER-SETTING MANUAL
VARMECA 10
Variable speed motors and geared motors
GENERAL INFORMATION
LEROY-SOMER
Ref. 3264 - 4.33/b -1.00
1.4.6 - Standard configuration: regulation with the integrated PI loop - PI reference using the local
button or external reference - 2 operating directions
Terminals
Specifications
1
+10 V analogue source
rated current: 3 mA
2
Analogue input
PI reference
3
Analogue input - PI sensor feedback
0 to +10 V - Impedance = 100 k
Ω
4
0 V - common with terminal 6
5
Logic input S1
PI reference selection
6
0 V - common with terminal 4
7
Logic input
run reverse/stop
8
Logic input
run forward/stop
9 - 10
Relay output 250 V - 1A
Switched off or faulty
On
1
2
3
4
5
6
7
9
L1
L2
L3
PE
10
8
Fault
relay
+10V
PI reference (local button
or external reference)
PI sensor feedback (0-10V)
0V
PI reference selection (local
button or external reference)
0V
Run reverse / stop
Run forward / stop
S1
MAINS
SUPPLY
Associated parameter setting
CDC-VMA
PEGASE VMA 10
Terminal block configuration
P14 = 0
STANDARD
P20 = 1
Terminal N˚3 assignment
PI input
PI reference selection
Reference
S1
switches
K1
K4
Local button
1
-
ON
Ext. ref. 0 - 10 V
0
ON
ON
Ext. ref. 4 - 20 mA
0
OFF
ON
Setting other parameters
see sections 2 and 3