PARAMETER-SETTING MANUAL
VARMECA 10
Variable speed motors and geared motors
COMMISSIONING THE CDC-VMA CONSOLE
LEROY-SOMER
Ref. 3264 - 4.33/b -1.00
2.3 - Read mode
- Power up the VARMECA 10.
- Connect the 230 V socket on the console power supply
unit.
- On power-up, the console display is positioned on the 1st
parameter PO1 FMIN.
The 1st line of the display unit indicates the parameter
designation.
The 2nd line indicates the parameter value and unit.
The
key is used for scrolling through parameters P01
to P29.
The
key is used for scrolling in the opposite direction.
2.4 - Parameter-setting mode
To modify a setting, use the
or
keys to select the
parameter.
The
key is used to make the parameter, which is to be
modified, flash.
Modify the setting value with the
or
keys.
As soon as the value differs from the stored value, the MEM?
message appears.
When the desired setting value has been reached, it can be
stored using the
key.
The MEM? indication disappears.
The
key is used to quit the parameter-setting mode.
If when the console is powered up, it is not
connected to the VARMECA 10 or if the VARMECA
10 is switched off, the message CONSOLE LINK
FAULT will appear
Parameter modifications must be performed with
the VARMECA 10 stopped (run command disabled)
MEM.