12
INSTALLATION AND MAINTENANCE
CPLS drip-proof 3-phase induction motors
4240 en - 2014.09 / b
LEROY-SOMER
Cable gland tables for the CPLS range of motors:
Cable gland type
Cable size
min. cable Ø (mm)
max. cable Ø (mm)
ISO 16 (for accessories)
5
10
ISO 20
9.5
15
ISO 25
13
19
ISO 32
15
25
ISO 40
21
32
ISO 50
26
38
ISO 63
31
44
Power supply cable cross-sections
The higher the current, the greater the voltage drop along the
cables will be (NFC 15.100 standard). The voltage drop should
therefore be calculated
for the maximum current absorbed
by the motor
to see if this is suitable for the application.
The chart below can be used to select the conductors according
to the length of the supply cables and the starting current, in
order to limit the voltage drop to 3% maximum.
This table does not allow the installer to dispense with checking the protective systems.
1
2
3
4
5 6 7 8 9 10
2
3
4
5 6 7 8 9 100
2
3
4
5
2
3
4
5
6 7 8 9 1000
10
20
30
40
50
60
70
80
90
100
200
300
400
500
600
700
800
900
1000
Length in m
Maximum voltage drop 3% (three-phase circuits - copper cable)
Current in A
Starting current
1 1.5 2.5 4 6
10 16
35 50 75 90
25
Conductor cross-section