Leonics NB 1K25 Скачать руководство пользователя страница 9

- 13 -

3.2.1 LAN I/F: The communication port for connecting RS-232 cable from UPS to

                       computer.

3.2.2 UPS OUTPUT:  The output outlets for connecting loads to the UPS backup

                        power system (available in NB-series UPS only).

3.2.3 INPUT CABLE: The cable to connect to utility power line.

3.2.4 INPUT FUSE: The overload or short circuit protection at UPS input side.

3.2.5 OUTPUT FUSE: The overload or short circuit protection at UPS output side.

3.2.6 NO LOAD SHUT DOWN SWITCH: The switch to enable automatic shutdown

                      when there is no load and power fails.  (No load means the total power

                      consumption of all loads are lower than 10% of full load).

         3.2.7

BATTERY circuit breaker: The circuit breaker for protecting battery from over

load or short circuit current.

3.2.8 INPUT circuit breaker: The circuit breaker for protecting the UPS from over

load or short circuit current.

3.2.9 INPUT TERMINAL: The terminal for connecting power from utility line to the

UPS.

3.2.10 OUTPUT TERMINAL: The terminal for connecting to loads.

3.2.11 GROUND: The terminal for connecting to ground system.

3.2.12 MAINTENANCE BYPASS SWITCH (option): Turn this switch to position B when

UPS is under maintenance.

- 14 -

INSTALLATION

Model

Input cable (mm

2

)

Output cable (mm

2

)

Earth cable (mm

2

)

Battery cable (mm

2

)

NB2K25

2.5-4

1.5-2.5

2.5-4

-

NBP-3K25

4

2.5

2.5-4

-

NBP-5K25

6

4

4

-

NBP-6K25

6

6

6

-

NBP-0811

10

6-10

6

6

NBP-1011

16

16

10

6-10

4.1 Connect the RS-232 signal cable from the computer (if any) to the UPS at LAN I/F or

RS232-PC port.

4.2 Enable NO LOAD SHUTDOWN feature.  Slide NO LOAD SHUTDOWN switch to

position ON.  When power fails, the UPS will check whether the load is equal to 9%

or lower.  If it is, the UPS will shut down to save battery power.

Note: The factory default setting is OFF or disabled.

4.3 For NB7525 and NB 1K25; plug INPUT CABLE to utility power source.  Then, plug

loads' cables to the UPS OUTPUT sockets.

4.4 Cable size for installing NB 2K25, and NBP-series.

Note: If the cable is longer than 5 meters, the cable size must be increased.

4.5 For NB 2K25; connect the cable from INPUT TERMINAL to utility power source.  Then,

connect the cable from OUTPUT TERMINAL to loads as shown in Figure 1.  Please

refer to the cable sizing in 4.4.

Figure 1

Содержание NB 1K25

Страница 1: ...NBP series NB series TRUE ON LINE DOUBLE CONVERSION UPS LEN MAN UPS 068 Rev 3 00 2008 www leonics com e mail global_business leonics com U S E R S G U I D E ...

Страница 2: ...CONTENT SAFETY INSTRUCTIONS 1 INTRODUCTION 3 FRONT AND REAR PANEL 6 INSTALLATION 14 OPERATION 16 TROUBLESHOOTING 19 MAINTENANCE 20 ...

Страница 3: ... plugging and unplugging the load in order to avoid electric shock from touching two surfaces with different potential 1 1 8 It is recommended to connect the UPS to a three wire AC source two poles plus ground which connects to a protected circuit such as employs a fuse or automatic circuit breaker 1 2 CAUTION Safety guide for installation and operation 1 2 1 Install the UPS in dry location with g...

Страница 4: ... to avoid electric shock 1 3 5 Replace batteries with the same type and rating and follow the proper battery replacement procedure Vocabulary Load Any equipment which is plugged into the UPS and gets power from the UPS such as a computer printer fax machine or modem UPS NB Series and NBP series UPS VA The unit of UPS power rating showing its capacity 2 2 1 When utility power and loads are normal A...

Страница 5: ...on and turn off the UPS 3 1 2 FUNC button The button to mute alarm sound or turn on the LCD s back light The back light will turn off automatically in 10 seconds after release this button 3 1 3 LINE indicator The Indicates when utility line normally 3 1 4 RECTIFIER indicator The indicator is displayed when utility line normally It supplies power to the UPS in rectifier section and supplies power t...

Страница 6: ...al port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 2 14 BATTERY TERMINAL for NBP0811 and NBP1011 The teminal for connecting to extension battery unit 3 1 13 LCD DISPLAY The screen to displays Input voltage Vin Output voltage Vout Battery Level B and Load level LD as shown in the picture below Note The valu...

Страница 7: ...reaker OPTION Thecomponenttoswitchthepower source of loads to utility power when maintenance 3 1 18 SNMP AGENT OPTION The additional port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 1 19 NO LOAD SHUT DOWN SWITCH The switch to enable automatic shutdown when there is no load and power fails No load means the ...

Страница 8: ... 11 3 2 6 3 2 1 3 2 12 3 2 9 3 2 8 3 2 7 3 2 13 3 2 10 3 2 11 12 ...

Страница 9: ...loads 3 2 11 GROUND The terminal for connecting to ground system 3 2 12 MAINTENANCE BYPASS SWITCH option Turn this switch to position B when UPS is under maintenance 14 INSTALLATION Model Input cable mm2 Output cable mm2 Earth cable mm2 Battery cable mm2 NB2K25 2 5 4 1 5 2 5 2 5 4 NBP 3K25 4 2 5 2 5 4 NBP 5K25 6 4 4 NBP 6K25 6 6 6 NBP 0811 10 6 10 6 6 NBP 1011 16 16 10 6 10 4 1 Connect the RS 232 ...

Страница 10: ...rn on INPUT circuit breaker 5 1 2 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 2 3 Turn on BATTERY circuit breaker 5 1 3 Model NBP 0811 and NBP 1011 5 1 3 1 Turn on INPUT circuit breaker 5 1 3 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 3 3 Turn on BATTERY circuit breaker 5 1 3 4 Turn on OUTPUT circuit breaker Note When the UPS is out of order turn on...

Страница 11: ...ch as when user turns on computers When the loads consume power less than 125 for 10 seconds UPS switches back to normal operation mode 5 3 4 If you connect loads to UPS more than 100 OVERLOAD indicator is lit we recommend you to unplug some of them until load is less than 100 to let loads get high quality power from UPS and backup power from battery Note LEONICS suggests that for highest reliabil...

Страница 12: ... UPS is turned on UPS does not supply backup power when power fails No indicator displays at the panel when the UPS is turned on UPS does not supply backup power when power fails MODEL PROBLEM SOLUTION 20 6 2 How to turn on INPUT circuit breaker for NB2K25 NBP 3K25 NBP 5K25 NBP 6K25 NBP 0811 and NBP 1011 6 2 1 Turn off the UPS by pressing the POWER button at the front panel 6 2 2 Turn on the INPUT...

Страница 13: ...n user wants to use the UPS plug the INPUT CABLE to wall outlet utility line Turn on POWER button and wait until the ventilation fan blows Then turn on BATTERY circuit breaker 7 4 2 Model NB 2K25 NBP 3K25 NBP 5K25 and NBP 6K25 7 4 2 1 Turn off the UPS by pressing the POWER button at the front panel 7 4 2 2 Turn off the BATTERY circuit breaker 7 4 2 3 Turn off the INPUT circuit breaker 7 4 2 4 When...

Отзывы: